JOHNSON CONTROLS
94
FORM 150.62-NM9 (709)
UNIT CONTROLS
As an example of compressor staging (refer to Table 18),
a chiller with six compressors using a Cooling Setpoint
programmed for 45°F (7.20°C) and a Range Setpoint
of 10°F (5.56°C). Using the formulas in Table 19, the
control range will be split up into six (seven including
hot gas) segments, with the Control Range determining
the separation between segments. Note also that the
Cooling Setpoint is the point at which all compressors
are off, and Cooling Setpoint plus Range is the point
all compressors are on. Specifically, if the return water
temperature is 55°F (12.8°C), then all compressors will
be on, providing full capacity. At nominal gpm, this
would provide approximately 45°F (7.2°C) leaving
water temperature out of the evaporator.
If the return water temperature drops to 53.4°F (11.9°C),
one compressor would cycle off leaving five compres
-
sors running. The compressors would continue to cycle
off approximately every 1.7°F (.94°C), with the excep-
tion of hot gas bypass. Notice that the hot gas bypass
would be available when the return water temperature
dropped to 46.25°F (7.9°C). At this point one compres-
sor would be running.
Should the return water temperature rise from this point
to 46.7°F (8.2°C), the hot gas bypass would shut off, still
leaving one compressor running. As the load increased,
the compressors would stage on every 1.7°F (.94°C).
Also notice that Tables 18, 19 and 20 not only provide
the formulas for the loading (ON POINT) and unload-
ing (OFF POINT) of the system, the “STEP” is also
shown in the tables. The “STEP” is that sequence in
the capacity control scheme that can be viewed under
the OPER DATA key. Please refer to the section on the
DISPLAY/PRINT keys for specific information on the
OPER DATA key.
TABLE 18 –
COMPRESSOR STAGING FOR RETURN WATER CONTROL
*Unloading only
COMPRESSOR STAGING FOR RETURN WATER CONTROL
6 COMPRESSORS
COOLING SETPOINT = 45°F (7.2°C) RANGE = 10°F (5.6°C)
# OF COMP ON
0
*1+HG
1
2
3
4
5
6
RWT
45°F
46.25°F
46.7°F
48.3°F
50.0°F
51.7°F
53.4°F
55.0°F
(7.2°C)
(7.9°C)
(8.2°C)
(9.1°C)
(10.0°C)
(11.0°C)
(11.9°C)
(12.8°C)
TABLE 19 –
RETURN CHILLED LIQUID CONTROL FOR 5 & 6 COMPRESSORS (7 & 8 STEPS)
*STEP
COMPRESSOR
COMPRESSOR ON POINT
COMPRESSOR OFF POINT
0
0
SETPOINT
SETPOINT
1
1 W/HGB
SP + CR/8 (Note 1)
SETPOINT
2
1 NO HGB
SP + CR/6
SETPOINT
3
2
SP + 2*CR/6 (Note 2)
SP + CR/6
4
2
SP + 2*CR/6
SP + CR/6
(Note 3)
5
3
SP + 3*CR/6
SP + 2*CR/6
6
4
SP + 4*CR/6
SP + 3*CR/6
7**
5
SP + 5*CR/6
SP + 4*CR/6
8
6
SP + CR
SP + 5*CR/6
NOTES:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
** 5-Compressor Chillers stop at 7 steps
Summary of Contents for YORK YCAL0043E Series
Page 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Page 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Page 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...