Function and Control
Domestic Air Conditioner
26
Increasing the frequency (1HZ/10second)
98
Increasing the frequency
˄
1HZ/1second
˅
TTC>=110
ć
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
5.2.6.2
˖
TC high temperature-preventing control of the indoor heating unit
˖
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running
state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 55
, decrease the rotate speed of the compressor and do the high
ć
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than 47
, recover to the normal control.
ć
TC The compressor stops
Fgh_t1
ˉ
2 Fgh_t1 65
ć
N Decreasing the frequency rapidly Fgh_t2 63
ć
Fgh_t2
ˉ
2 P Decreasing the frequency slowly
Fgh_t3 55
ć
Fgh_t3
ˉ
2 Q Prohibiting increasing the frequency
Fgh_t4 52
ć
Fgh_t4—2 R Increasing slowly Fgh_t5 48
ć
Fgh_t5—2
Normal
N
˖
Decreasing at the speed of 1HZ/1 second
P
˖
Decreasing at the speed of 1Hz/10 seconds
Q
˖
Continue to keep the last-time instruction cycle
R
˖
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
5.2.6.3 The control of preventing the overcurrent of the compressor
˖
●During the starting process of the compressor, if the curren of the compressor is greater than 12A for
3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
●During the starting process of the compressor, if the AC current is greater than 11A, the frequency of
the compressor decreases at the speed of 1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 10A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 9.5A, the frequency
of the compressor increases at the prohibited speed.
●During the starting process of the compressor, if the AC current is greater than 9A, the
YJHJZH024BARRAFX
-SM
Summary of Contents for YJHJXH024BARR-FX
Page 44: ...1 6 2 1 The Instruction For AS24GS1ERA YJHJZH024BARRAFX SM...
Page 82: ...79 Domestic air conditioner Installation WARNING CAUTION YJHJZH024BARRAFX SM...
Page 83: ...80 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 86: ...Installation 83 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 87: ...Installation 84 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 88: ...Installation 85 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 91: ...88 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 92: ...e g 1U18FS1ERA 89 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 123: ...The end YJHJZH024BARRAFX SM...