Function and Control
Domestic Air Conditioner
15
5.1.3 Demoisture mode.
* temperature control range: 16---30
ć
* temperature difference:
r
1
ć
Control feature: send the demoisture signal to the outdoor system.
When Tr>Ts+2
, the compressor will be turned on, the indoor fan will opera
ć
te at the set speed.
When Tr is between the Ts and Ts+2
, the outdoor system will operate at the high demoisture
ć
frequency for 10 minutes and then at the low demoisture mode for six minutes. The indoor fan
will operate at low speed.
When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option.
All the frequency converses have a ±1
difference.
ć
* Wind speed control: Automatic:
When Tr >= Ts+ 5
, high speed.
ć
When Ts+3
ć
d
Tr< Ts+5
, medium sp
ć
eed.
When Ts+2
ć
d
Tr< Ts+3
, low speed.
ć
When Tr<Ts+2
, light speed.
ć
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the
system will be changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be
delayed for 3 minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3
, the manual opera
ć
tion can not be made. (obligatory
automatic operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM)
and the temperature of the indoor coils has been below zero centigrade for 10 seconds, the
compressor will be stopped and the malfunction will be recorded in the malfunction list. The
indoor system will continue to run. When the temperature of the indoor coil is raised to 7
, the
ć
compressor will be restarted again (the prerequirement of 3 minutes’ delay should be satisfied.)
* coil protection (synchronic overheating protection) are installed for the four directions latch
malfunctions when demoisturing.
* timing system on/off function.
* Dormant control function.
5.1.4 Heating operation mode.
* temperature control range: 16---30
ć
* temperature difference:
r
1
ć
* control feature: the temperature compensation is automatically added and the system will send the
heating signals to the outdoor system.
If Tr
d
Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode.
If Tr>Ts+3, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
If Tr<Ts+3
ˈ
the outdoor system will be turned on again, the indoor fan will be at the cold air proof
YJHJZH024BARRAFX
-SM
Summary of Contents for YJHJXH024BARR-FX
Page 44: ...1 6 2 1 The Instruction For AS24GS1ERA YJHJZH024BARRAFX SM...
Page 82: ...79 Domestic air conditioner Installation WARNING CAUTION YJHJZH024BARRAFX SM...
Page 83: ...80 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 86: ...Installation 83 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 87: ...Installation 84 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 88: ...Installation 85 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 91: ...88 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 92: ...e g 1U18FS1ERA 89 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 123: ...The end YJHJZH024BARRAFX SM...