Service Diagnosis
Domestic Air Conditioner
65
7.4.2 Indoor fan motor malfunction
,QGRRU'LVSOD\
(
0HWKRGRI
The rotation speed detected by the Hall IC during fan motor operation is used to determine
0DOIXQFWLRQ
abnormal fan motor operation
'HWHFWLRQ
0DOIXQFWLRQ
when the detected rotation feedback singal don’t receiced in 2 minutes
'HFLVLRQ
&RQGLWLRQV
6XSSRVHG &DXVHV
Ƶ
Operation halt due to breaking of wire inside the fan motor .
Ƶ
Operation halt due to breaking of the fan motor lead wires
Ƶ
Detection error due to faulty indoor unit PCB
+RZWRFKHFN)DQ0RWRU'&
1. Check connector connection.
2. Check motor power supply voltage output (pins 1-4).
3. Check motor control voltage (pins 4-5).
4. Check rotation command voltage output (pins 4-6).
5. Check rotation pulse input (pins 4-7).
Notes:the a/c is electrifying,don’t pull out or insert the terminals of the
motor,else the motor would be damaged
Troubleshooting
&DXWLRQ
Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
YJHJZH024BARRAFX
-SM
Summary of Contents for YJHJXH024BARR-FX
Page 44: ...1 6 2 1 The Instruction For AS24GS1ERA YJHJZH024BARRAFX SM...
Page 82: ...79 Domestic air conditioner Installation WARNING CAUTION YJHJZH024BARRAFX SM...
Page 83: ...80 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 86: ...Installation 83 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 87: ...Installation 84 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 88: ...Installation 85 Domestic air conditioner YJHJZH024BARRAFX SM...
Page 91: ...88 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 92: ...e g 1U18FS1ERA 89 Domestic air conditioner Installation YJHJZH024BARRAFX SM...
Page 123: ...The end YJHJZH024BARRAFX SM...