Series II Installation Manual Addendum
LIT-12012316
Effective
May
2017
www.johnsoncontrols.com
15
Cable Power and Motor Wiring Guidelines
Frame
Amp
Suf-
fix
hp
VSD
I(L)
Amps
at 40°C
VSD
I(L)
Amps
at 50°C
Fuse
Rating
(Class
T)
NEC Wire Size
(AWG)
Terminal Connection Size
(AWG)
Line and
Motor
Ground
Line and Mo-
tor
Ground
FR5
3D9
3
3.9
3.3
6
14
12
20-5
17-8
6D1
5
6.1
5.2
10
14
12
20-5
17-8
009
7.5
9
7.7
10
14
10
20-5
17-8
011
10
11
9.4
15
14
8
20-5
17-8
FR6
018
15
18
15
20
10
8
13-0
13-2
022
20
22
18
25
10
8
13-0
13-2
027
25
27
23
30
8
8
13-0
13-2
034
30
34
28
40
8
6
13-0
13-2
FR7
041
40
41
34
50
6
6
9-2/0
9-2/0
052
50
52
44
60
6
6
9-2/0
9-2/0
062
60
62
52
70
4
4
9-2/0
9-2/0
FR8
080
75
80
68
90
1/0
2
1 AWG -350
kcmil
1 AWG -350
kcmil
100
100
100
85
110
1/0
0
1 AWG -350
kcmil
1 AWG -350
kcmil
125
125
125
106
150
2/0
2/0
1 AWG -350
kcmil
1 AWG -350
kcmil
FR9
144
150
144
122
175
3/0
3/0
1 AWG -350
kcmil
1 AWG -350
kcmil
208
200
208
176
250
300
kcmil
300
1 AWG -350
kcmil
1 AWG -350
kcmil