New Control Board Installation Requirements

The new control board launched to provide additional capabilities to the Series II product including LED
indication, dip switch operation and improved processing power.  There is a change in the control terminal
landing locations, the battery for the real time clock and dip switch functionality.

Control Board

The main Series II Series VSD consists of a main control board, control I/O connections block and two
slots for extra option boards.

A. The control terminals for the standard I/O connections
B. The Ethernet connection

C.

The relay board terminals for 3 relay outputs or 2 relay outputs and a thermistor

D. The option boards

E.

A DIP switch for the RS485 bus termination

F.

A DIP switch for the signal selection of Analog Output

G.

A DIP switch for the isolation of the digital inputs from ground

H. A DIP switch for the signal selection of Analog Input 2

I.

A DIP switch for the signal selection of Analog Input 1

J.

The status indicator of the Ethernet Connection

K. A fan (only in IP54 of FR4 and of FR5)
L.

The battery for the RTC

M. The location and the default position of the Safe Torque Off (STO) jumper

NOTE: Option board location C is not active and will not support I/O expansion cards not
communication cards

Summary of Contents for VSD II Series

Page 1: ...Variable Speed Drive Series II LIT 12012316 JCI VSD Series II Installation Manual Addendum New control board update 525 600V offering Effective May 2017...

Page 2: ...a Johnson Controls Return Mate rial Authorization RMA number prior to returning any defective product When purchased through an Authorized Distributor the Distributor should supply an RMA number to th...

Page 3: ...son Controls PSO Team if you need assistance with placing an order stock availability or proof of shipment expediting an existing order emergency shipments product price information and returns includ...

Page 4: ...Number Selection 10 Power Ratings and Product Selection 11 Mounting Drive Dimensions 12 Series II Technical Data 13 Cable Power and Motor Wiring Guidelines 15 Manual Addendum This manual is an addend...

Page 5: ...ards A The control terminals for the standard I O connections B The Ethernet connection C The relay board terminals for 3 relay outputs or 2 relay outputs and a thermistor D The option boards E A DIP...

Page 6: ...linking slowly Ready Green Run Red Fault Orange Alarm Blinking fast Downloading software Control Board Terminals Here is the basic description of the terminals of the standard I O board Control Wiring...

Page 7: ...he DIP switches for specified terminals The switches have 2 positions up and down You can see the location of the DIP switches and the possible selections below A The voltage signal U 0 10 V input B T...

Page 8: ...n of a DIP switch on the control board A The digital inputs B Floating C Connected to GND default Field Bus Connection You can connect the drive to fieldbus with an RS485 or an Ethernet cable If you u...

Page 9: ...y board terminals and other terminals The terminal The terminal screw The tightening torque Nm lb in All the terminals of the I O board and the relay board M3 0 5 4 5 Battery for Real Time Clock To us...

Page 10: ...0V Catalog Number Selection SERIES II Series Open Drives Notes All boards are varnished conformed coated Corrosion resistant Battery included in all drives for real time clock Three year lifetime Keyp...

Page 11: ...Full Load Amps at 50 C 1 N1 IP21 2 N12 IP54 Catalog Number FR5 3 9 3 4 6 3 3 VS3D95_0B 00000 6 1 5 6 8 5 2 VS6D15_0B 00000 9 7 5 9 7 7 VS9D05_0B 00000 11 10 10 5 9 4 VS0115_0B 00000 FR6 18 15 19 9 15...

Page 12: ...Line Voltage hp VT Amperes D H1 H2 H3 W1 W2 W3 Weight in Lbs FS5 600 Vac 3 10 3 9 11 8 73 16 5 15 98 15 04 5 67 4 53 3 94 22 FS6 600 Vac 15 30 18 34 9 29 21 93 21 28 20 24 7 68 5 83 5 83 44 1 FS7 600...

Page 13: ...tion 0 1 3000 sec Ambient conditions Ambient operating temperature IL 10 C no frost to 40 C up to 50 C with derating Storage temperature 40 to 70 C Relative humidity 0 95 RH non condensing non corrosi...