Series II Installation Manual Addendum
14
www.johnsoncontrols.com
LIT-12012316
Effective
May
2017
Series II
Technical Data, continued
Attribute
Description
Specification
EMC (at default
settings)
Immunity
Fulfils EN61800-3 (2004), first and second environment
Emissions
EN61800-3 (2004), Category C3
The drive can be modified for IT-networks
Noise level
Average noise level
(cooling fan) sound pow-
er level in dB (A)
FS5: 65
FS8: 73
FS6: 72
FS9: 75
FS7: 73
Safety
-
EN61800-5-1 (2007), CE, cUL (see nameplate for more
detailed approvals)
Protections
Overvoltage trip limit
600V drives: 1094Vdc
Undervoltage trip limit
Depends on supply voltage (0,8775*supply voltage):
Supply voltage 600V: Trip limit 527V
Eart fault protection
Yes
Mains supervision
Yes
Motor phase supervision
Yes
Overcurrent protection
Yes
Unit overtemperature
protection
Yes
Motor overload protection
Yes
Motor stall protection
Yes
Motor underload protec-
tion
Yes
Shart-circuit protection of
24V and 10V reference
voltage
Yes