FlexSys
Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local
Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
36
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
Repair Information
If the TEC3000 Series Thermostat Controller fails to
operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest
Johnson Controls representative.
The controller displays
Board
Mismatch
.
The I/O board that the display board is
currently attached to does not match
the one that initially shipped with the
display board.
Attach the display board to the correct
I/O board.
A hardware failure is causing the two
boards to incorrectly identify
themselves.
Contact Johnson Controls product
sales and support.
The controller displays
Controller
Fault
.
An internal fault was detected and the
controller was unable to recover.
Contact Johnson Controls product
sales and support.
The Bell icon is displayed on the TEC
home page.
The fault has been detected on the
TEC.
See Table 8 for TEC fault causes and
resolution.
Partial Restore Complete
is displayed
when trying to restore settings from a
backup file.
Not all of the items in the backup file
have been restored. This error can be
caused by a value being out of the
minimum or maximum range in the
backup file. It may also occur if there
are inconsistencies in
the reliability of a
setting in the backup file and on the
TEC device.
1. Create a Backup file on a USB
drive for the TEC that is showing
the issue.
2. Edit the backup file created in step
1 on a PC to reflect the desired
settings.
3. Verify that the modified values are
within minimum and maximum
range in the backup file.
4. Restore the settings from the newly
edited backup file on the TEC.
1. For common MS/TP troubleshooting information, refer to the
MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
Table 9: Troubleshooting Details
1
(Part 3 of 3)
Symptom
Probable Causes
Solutions