FlexSys
Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local
Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
27
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
27
Network Setup
FC Comm Mode
BACnet/MSTP
BACnet/MSTP, N2
BACnet Instance ID*
4
0 to 4,194,302
* BACnet/MSTP communication mode
N2 Device Address*
1
1 to 255
* N2 communication mode
BACnet Device Address*
4
4 to 127
* BACnet/MSTP communication mode
MSTP Baud Rate*
Auto
Auto, 1200, 9600, 19200, 38400, 76800
* BACnet/MSTP communication mode
BACnet Encoding Type
BACnet/MSTP Communication Mode
ISO 10646
(UCS-2)
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)
Equipment Setup
General
Unit Type
4-Pipe
2-Pipe, 4-Pipe, VAV
Heating/Cooling Device Type*
Floating
On/Off, Floating
* Fan coil units only
Actuator Stroke Time*
30 seconds
5 to 300
* Floating Heating/Cooling device type
only
Cooling Min On Time*
120 seconds
0 to 360 seconds
* Fan coil on/off units only
Cooling MIn Off Time*
120 seconds
0 to 360 seconds
* Fan coil on/off units only
Heating Min On Time*
120 seconds
0 to 360 seconds
* Fan coil on/off units only
Heating Min Off Time
120 seconds
0 to 360 seconds
* Fan coil on/off units only
Table 6: Menus and Submenus (Part 4 of 7)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values