Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
Configuring Occupancy
The TEC3000 controller supports a wide variety of
occupancy sources in order to adapt to nearly any
application.
•
Local stand-alone weekly scheduler
•
Remote schedule from BAS
•
Occupancy sensor (internal or remote)
•
Occupancy binary input (configurable)
•
Manual occupancy override
•
Temporary occupancy (by interacting with screen
while unoccupied)
•
Temporary occupancy binary input
Occupancy is determined using a top-down decision
matrix as shown in Table 4.
Selecting Schedule Source
The occupancy schedule comes from either the weekly
scheduler built into the TEC or as an input from the
BAS. The Schedule Source must be selected to tell the
controller where to read the occupancy source from. To
select the schedule source:
1. Press the Menu icon.
2. Press
Schedule
.
3. Press
Schedule Options
.
4. Press
Schedule Source
and select Local or BAS.
Table 4: Occupancy Determination
Effective Occupancy
Criteria
Occupancy
Source
Occupancy
Status
Manual
Occupancy
Mode
Occupancy
BI
Temporary
Occupancy
Occupancy
Schedule
(Local or
BAS)
Motion
Sensor
Occ Override
Occupied-
Override
Occupied
–
–
–
–
Unoccupied-
Override
Unoccupied
Occupancy BI
Occupied
No Override
Closed
1
Unoccupied
Open
1
Temp Occ
Temp
Occupancy
Not
Configured
1
True
2
NOT Occupied
Temp Occ BI
Temp
Occupancy
True
3
NOT Occupied
Occupancy
Sensor
Occupied
False
Occupied
True
Standby
False
Occupancy
Schedule
Occupied
Disabled
Unoccupied
Unoccupied
–
Standby
Standby
Occupancy
Sensor
Occupied
Not Set
4
True
Unoccupied
False
Occupancy
Schedule
Occupied
Disabled
1. Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current
state of the BI when configured as Occupancy BI.
2. True is triggered by interacting with the screen during scheduled unoccupied period. A value of True can only occur when
schedule is not Occupied.
3. When triggered by a BI configured for Temp Occ., the input is ignored when the schedule is Occupied, the Manual
Occupancy Mode is NOT No Override, or an Occupancy BI is configured.
4. Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to BAS and the
BAS is writing Not Set as the schedule.