FlexSys
Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local
Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
1
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with
Dehumidification Capability Installation Instructions
QuickLIT website
for the most up-to-date version of this document.
Applications
The TEC3000 Series On/Off or Floating Fan Coil and
Zoning Thermostat Controllers are stand-alone and
field-selectable BACnet® Master-Slave/Token-Passing
(MS/TP) or N2 networked devices provide control of:
•
local hydronic reheat valves
•
pressure-dependent variable air volume (VAV)
equipment with or without local reheat
•
two- or four-pipe fan coils
•
cabinet unit heaters
•
other zoning equipment using an on/off or floating
control input
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or
N2 communication capability that enables remote
monitoring and programming for efficient space
temperature control. All models include a USB port
configuration that reduces installation time by allowing
simple backup and restore features from a USB drive,
which enables rapid cloning of configuration between
like units.
Some models have occupancy sensing capability built
into the device. These thermostat controllers maximize
up to 30% energy savings in high-energy usage
commercial buildings, such as schools and hotels,
during occupied times by using additional standby
setpoints.
All models feature an intuitive UI with backlit display
that makes setup and operation quick and easy.
Multiple fan configurations are supported for fan coil
equipment types:
•
single-speed
•
multi-speed (two or three discrete speeds)
•
variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan
coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the
thermostat controller monitors space humidity and
activates dehumidification control as necessary. Heat
and/or reheat is used as required to maintain the space
temperature. For optimal dehumidification
performance, use a fan coil unit that has a multi-speed
or variable-speed fan (VSF).
IMPORTANT:
The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
thermostat controller.
IMPORTANT :
Le TEC3000 Series Thermostat
Controller est destiné à transmettre des données
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du thermostat controller
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du thermostat
controller.
TEC3310-00-000, TEC3311-00-000, TEC3312-00-000, TEC3313-00-000,
TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, TEC3613-00-000