5538117-UIM-B-0319
8
Johnson Controls Ducted Systems
TABLE 6:
Electrical Data for 208/230-3-60 Single Source Power
Model
Compressor
OD
Fan
Motor
Blower
Motor
Electric Heat Option
MCA
1
1. Minimum Circuit Ampacity.
Max Fuse
2
or Breaker
3
Size
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
Heater Kit
4
4. Single Point Connection Kit required.
Heater
kW
Stages
Heater
Amps
Total
Unit
Unit
Less
Heater
Unit
Heater
Only
Total
Unit
Unit
Less
Heater
Unit
Heater
Only
RLA LRA MCC FLA
FLA
208 230
208 230 208 230 208 230 208 230 208 230 208 230 208 230
PCE4A36 10.4 73.0 16.3
1.3
3.8
none
--
--
--
--
--
18.1 18.1 18.1 18.1
-
-
25
25
25
25
-
-
6HK06501025 7.2 8.8
1
20.0 22.1 28.8 31.5 18.1 18.1 25.0 27.6 30
35
25
25
25
30
6HK06501525 10.8 13.2
1
30.0 33.2 41.3 45.3 18.1 18.1 37.5 41.5 45
50
25
25
40
45
PCE4B48 13.7 83.1 21.4
1.7
5.4
none
--
--
--
--
--
24.2 24.2 24.2 24.2
-
-
35
35
35
35
-
-
6HK06501025 7.2 8.8
1
20.0 22.1 30.4 33.1 24.2 24.2 25.0 27.6 35
35
35
35
25
30
6HK06501525 10.8 13.2
1
30.0 33.2 42.9 46.9 24.2 24.2 37.5 41.5 45
50
35
35
40
45
6HK06501825 13.0 15.9
2
36.1 39.9 50.5 55.2 24.2 24.2 45.1 49.8 60
60
35
35
50
50
6HK16502025 14.4 17.6
2
40.0 44.3 55.4 60.7 24.2 24.2 50.0 55.4 60
70
35
35
*
*
PCE4B60 16.0 110.0 24.9
1.7
7.0
none
--
--
--
--
--
28.7 28.7 28.7 28.7
-
-
40
40
40
40
-
-
6HK06501025 7.2 8.8
1
20.0 22.1 32.0 34.7 28.7 28.7 25.0 27.6 40
40
40
40
25
30
6HK06501525 10.8 13.2
1
30.0 33.2 44.5 48.5 28.7 28.7 37.5 41.5 45
50
40
40
40
45
6HK06501825 13.0 15.9
2
36.1 39.9 52.1 56.8 28.7 28.7 45.1 49.8 60
60
40
40
50
50
6HK16502025 14.4 17.6
2
40.0 44.3 57.0 62.3 28.7 28.7 50.0 55.4 60
70
40
40
*
*
6HK16502525 18.0 22.0
2
50.0 55.3 69.5 76.2 28.7 28.7 62.5 69.1 70
80
40
40
*
*
NOTES:
Single-source power MCA and MOP requirements are given here only for reference if the unit is to be installed with a field-installed single-point power modifica-
tion.
*
Breakers for heaters are included in the 20kW and 25kW heater kits.
TABLE 7:
Electrical Data for 208-3-60 Multi Source Power
Model
Compressor
OD Fan
Motor
Blower
Motor
Electric Heat Option
Multi Source
Heater Kit
Heater kW
Stages
Heater Amps
RLA
LRA
MCC
FLA
FLA
208
208
208
208
208
208
208
208
Multi Source: Compressor
Circuit and Heat Circuits
Multi Source:
Circuit #1 Compressor Circuit
Circuit #2 Heat
Circuit #3 Heat
MCA
1
Amps
MOP
2
MCA
1
Amps
MOP
2
MCA
1
Amps
MOP
2
Circuit #1
Circuit #2
Circuit #3
PCE4A36 10.4
73.0
16.3
1.3
3.8
none
--
--
--
18.1
25
--
--
--
--
6HK06501025
7.2
1
20.0
18.1
25
25.0
25
--
--
6HK06501525
10.8
1
30.0
18.1
25
37.5
40
--
--
PCE4B48 13.7
83.1
21.4
1.7
5.4
none
--
--
--
24.2
35
--
--
--
--
6HK06501025
7.2
1
20.0
24.2
35
25.0
25
--
--
6HK06501525
10.8
1
30.0
24.2
35
37.5
40
--
--
6HK06501825
13.0
2
36.1
24.2
35
45.1
50
--
--
6HK16502025
14.4
2
40.0
24.2
35
25.0
25
25.0
25
PCE4B60 16.0
110.0
24.9
1.7
7.0
none
--
--
--
28.7
40
--
--
--
--
6HK06501025
7.2
1
20.0
28.7
40
25.0
25
--
--
6HK06501525
10.8
1
30.0
28.7
40
37.5
40
--
--
6HK06501825
13.0
2
36.1
28.7
40
45.0
50
--
--
6HK16502025
14.4
2
40.0
28.7
40
25.0
25
25.0
25
6HK16502525
18.0
2
50.0
28.7
40
31.3
35
31.3
35
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.