5538117-UIM-B-0319
12
Johnson Controls Ducted Systems
1. Airflow tested with dry coil conditions, without air filters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
TABLE 11:
Airflow Performance - Bottom Duct Application
Model
Motor Speed
External Static Pressure (Inches WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.0
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
PCE4A36
Low (1)
1231
1186
1146
1103
1069
1030
977
912
781
Low/Medium (2)
1270
1225
1189
1140
1098
1046
1008
960
866
Medium (3)
1317
1286
1245
1198
1151
1110
1064
1024
943
Medium/High (4)
1358
1317
1275
1238
1197
1148
1105
1057
961
High (5)
1517
1475
1447
1400
1357
1318
1275
1232
1146
PCE4B48
Low (1)
1598
1548
1502
1454
1410
1362
1307
1251
1139
Low/Medium (2)
1663
1612
1568
1522
1476
1422
1370
1297
1152
Medium (3)
1789
1733
1670
1650
1596
1578
1535
1483
1379
Medium/High (4)
1931
1814
1808
1736
1673
1650
1597
1519
1362
High (5)
2131
2058
1998
1949
1892
1840
1788
1728
1608
PCE4B60
Low (1)
1655
1612
1596
1531
1461
1462
1429
1391
1316
Low/Medium (2)
1766
1720
1667
1629
1632
1539
1537
1498
1421
Medium (3)
1987
1933
1861
1817
1820
1715
1725
1651
1504
Medium/High (4)
2114
2050
2047
1974
1899
1889
1920
1866
1758
High (5)
2369
2308
2249
2183
2126
2088
2034
1990
1902
TABLE 12:
Electric Heat Minimum Supply Air
Model
Voltage
Minimum Blower Speed for Electric Heat
Heater kW
2
5
8
10
13
15
18
20
25
PCE4A36
208/230-3-60
Low #1 Low #1
Low #1
Low #1
Med. Low #2
High #5
--
--
--
PCE4B48
208/230-3-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. High #4
--
PCE4B60
208/230-3-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. High #4
TABLE 13:
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
Nominal
Applied
240
208
0.75
230
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.