5538117-UIM-B-0319
10
Johnson Controls Ducted Systems
TABLE 9:
Physical Data
NOMINAL TONNAGE
MODELS
PCE4A36
PCE4B48
PCE4B60
3.0
4.0
5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
37.2
47.7
55.0
AHRI net capacity (MBH)
35.2
45.5
52.5
EER
11.0
11.0
11.0
SEER
14.0
14.0
14.0
Nominal CFM
1150
1550
1750
System power (KW)
3.2
4.2
4.8
Refrigerant type
R410A
R410A
R410A
Refrigerant charge (lb-oz)
8-8
11-3
12-0
Dimensions (inches)
Length
51-1/4
51-1/4
51-1/4
Width
35-3/4
45-3/4
45-3/4
Height
47
49
51
Operating WT. (lbs.)
382
455
472
Compressors
Type
Scroll
Scroll
Scroll
Outdoor Coil Data
Face area (Sq. Ft.)
15.1
19.5
21.5
Rows
2
2
2
Fins per inch
22
22
22
Tube diameter
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Indoor Coil Data
Face area (Sq. Ft.)
4.6
6.3
6.3
Rows
3
3
3
Fins per inch
16
16
16
Tube diameter
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Refrigerant control
TXV
TXV
TXV
Outdoor Fan Data
Fan diameter (Inch)
24
26
26
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
No. speeds
1
1
1
Motor HP each
1/4
1/3
1/3
RPM
850
850
850
Nominal total CFM
2400
4200
4200
Direct Drive Indoor Fan Data
Fan Size (Inch)
11 x 10
11 x 10
11 x 10
Type
Centrifugal
Centrifugal
Centrifugal
Motor HP each
1/2
3/4
1
RPM
1200 Max
1200 Max
1200 Max
Frame size
48
48
48
Filters
Filter Size
A
B
B
Quantity - Size
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through dispos-
able filters. For internal filter use, a filter rack kit is included with all three phase models. Consult the
instructions supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.