English
IS_M9116-GGx-1N4 / M9108-GGx-1N4_14-88360-2080_Rev. C_12 2009
This document is subject to change without notice
2
70°
: Rotate the adapter
(Figure 2 f.)
in the same manner as
before to the 70° position. Slightly loosen the Phillips screw in
the cam wheel
b.
so that the wheel can be moved by hand.
Rotate the cam wheel
b. clockwise
until the switch button
can be seen. Then tighten-back the Phillips screw in the cam
wheel
b.
.
Factory setting of auxiliary switches
The two auxiliary switches
a.
and
b.
are factory set at the to
approximately 10° CW (
a.
) and 80° CW (
b.
).
Ordering Codes
Codes
Descriptions
M9116-GGA-1N4
Actuator AC/DC 24 V
M9116-GGC-1N4
Actuator AC/DC 24 V with 2 auxiliary switches
M9108-GGA-1N4
Actuator AC/DC 24 V
M9108-GGC-1N4
Actuator AC/DC 24 V with 2 auxiliary switches
Technical Specifications
Actuators
M9116-GGx-1N4
M9108-GGx-1N4
Drive torque
16 Nm
8 Nm
Damper area
3.0 m
2
1.5 m
2
Running time
16 s
8 s
Indipendent of load, at nominal conditions and room temperature
Power supply
AC 24 V ±20% / DC ±10%
Frequency
50-60 Hz
Power consumption:
- operating
6.0 W
- at end stops
0.6 W
For wire sizing
15.0 VA / 3.6 A @ 2ms
Weight
1.1 kg
Control signals:
Y1
0...10 V / Ri > 200 k
Ω
Y2
0...20 mA / Ri 388
Ω
Position signal
U
DC 0...10 V / R > 50 K
Ω
Angle of rotation:
- Working range
90° (93° mech.)
- Limiting
5°...85° in 5° steps
Auxiliary switch rating
3(1.5) A, AC 230 V
Sound power level
45 dB (A)
Protection class
II
Degree of protection
IP 54 (with cable glands, cable downwards)
Temperature: operating/store
-20°...+50°C / -30°...+60°C
Humidity
5...95% RH (not condensing).
Maintenance
Maintenance-free
Conformity
EMC Directive 2004/108/EC:
EN 55011:2007
EN 55022:2006 A1:2007
EN 61000-3-2:2006
EN 61000-3-3:2008
EN 61000-4-2:2001
EN 61000-4-3:2006
EN 61000-4-4:2007
EN 61000-4-5:2006
EN 61000-4-6:2007
EN 61000-4-8 :1994 A1:2001
EN 61000-4-11:2004
EN 61000-6-1:2007
EN 61000-6-3:2007
Low Voltage Directive 2006/95/EC:
EN 60730-1A:2002
EN 60730-2-14:2002