IOM4710 Input/Output Module Installation Instructions

7

Configurable 
OUT

OUT 

n

Analog Output, Voltage Mode
Sources 0-10 VDC.
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current

A

Binary Output, 24 VAC Triac Mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
40 mA minimum load current
0.5 A maximum output current, or 
1.3 A at 25% duty cycle, or
Maximum 6 cycles per hour with M9220-BGx-3

C

OCOM 

n

Analog Output:  The signal common for 

all

 

analog-configured CO terminals; isolated from all other 
terminal commons, excluding BI terminal commons.
Binary Output:  The signal common for binary-configured 
CO terminals; isolated from 

all

 other terminal commons, 

including other CO terminal commons.

Same as OUT

SA/FC Bus 
Port

1,2

SA/FC Bus

Provides SA Bus communication network.
RJ-12 6-position modular connector

30.5 m (100 ft) maximum length 
phone cord

SA Bus

1,2

+
-
COM

Provides SA Bus communication network.

Daisy-chained
366 m (1,200 ft) maximum length
0.6 to 1.5 mm 
(18 to 24 AWG)
[22 AWG Recommended]

FC Bus

2

+
-
COM

Provides FC Bus communication network.

Daisy-chained
1,524 m (5,000 ft) maximum length
0.6 to 1.5 mm 
(18 to 24 AWG)
[22 AWG Recommended] 

SHLD

Provides an optional shield connection.

24~ Power

Hot

AC Supply Input
Supply 20-30 VAC (Nominal 24 VAC)

16 AWG

COM

The 24~ Power common; isolated from all other terminal 
commons

1.

The SA Bus and the SA/FC Bus Port are daisy-chained internally.

2.

The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more 
information, refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

Table 1:  FEC/IOM Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 3 of 3)

Terminal 
Block

Terminal 
Labels

Function and Electrical Ratings/Requirements

Wiring Requirements
(See Table 2 for A, B, or C.)

Summary of Contents for IOM4710

Page 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Page 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Page 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Page 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Page 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Page 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Page 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Page 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Page 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Page 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Page 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Page 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Reviews: