IOM4710 Input/Output Module Installation Instructions
6
Analog OUT
OUT
n
Analog Output, Voltage Mode
Sources 0-10 VDC output voltage.
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
A
Analog Output, Current Mode
Sources 4-20 mA output current.
External 300 ohm maximum load required
B
OCOM
n
The signal common for all Analog OUT terminals;
isolated from all other terminal commons.
Same as OUT
Binary OUT
(Jumper Set
to External)
OUT
n
Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
40 mA minimum load current
0.5 A maximum output current, or
1.3 A at 25% duty cycle, or
Maximum 6 cycles per hour with M9220-BGx-3
C
OCOM
n
The signal common for Binary OUT terminals; isolated
from all other terminal commons, including BO terminal
commons.
Binary OUT
(Jumper Set
to Internal)
OUT
n
Sources 24~ Power (Hot)
C
OCOM
n
Binary Output, 24 VAC Triac
Connects OCOM to 24~ Power (Com) when activated.
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current
Table 1: FEC/IOM Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements
Wiring Requirements
(See Table 2 for A, B, or C.)