background image

IOM4710 Input/Output Module Installation Instructions

6

Analog OUT

OUT 

n

Analog Output, Voltage Mode
Sources 0-10 VDC output voltage.
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current

A

Analog Output, Current Mode
Sources 4-20 mA output current.
External 300 ohm maximum load required

B

OCOM 

n

The signal common for all Analog OUT terminals; 
isolated from all other terminal commons.

Same as OUT

Binary OUT
(Jumper Set 
to External)

OUT 

n

Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
40 mA minimum load current
0.5 A maximum output current, or
1.3 A at 25% duty cycle, or
Maximum 6 cycles per hour with M9220-BGx-3

C

OCOM 

n

The signal common for Binary OUT terminals; isolated 
from all other terminal commons, including BO terminal 
commons.

Binary OUT
(Jumper Set 
to Internal)

OUT 

n

Sources 24~ Power (Hot)

C

OCOM 

n

Binary Output, 24 VAC Triac
Connects OCOM to 24~ Power (Com) when activated.
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current

Table 1:  FEC/IOM Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 3)

Terminal 
Block

Terminal 
Labels

Function and Electrical Ratings/Requirements

Wiring Requirements
(See Table 2 for A, B, or C.)

Summary of Contents for IOM4710

Page 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Page 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Page 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Page 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Page 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Page 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Page 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Page 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Page 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Page 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Page 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Page 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Reviews: