Note:

 Switch 128 on the device address DIP switch 

block enables or disables an FEC to operate on a 
ZFR1800 Series Wireless Field Bus. Position switch 
128 Off for wired FC bus applications. Position switch 
128 On only for wireless bus applications.

Setting the FC Bus or SA Bus Address

For most devices on an FC Bus or SA Bus, the 
(non-supervisory) device address is set using the DIP 
switches on the device’s ADDRESS DIP switch block. 
The DIP switch blocks are binary switch blocks, and 
each switch represents a binary numerical value when 
the switch is set to the ON position. For example, 
positioning switches 16, 4, and 1 to ON, as shown in 
Figure 11 sets the device address to 21. 

FC Bus or SA Bus EOL Switch

The EOL switch applies power termination to the 
device’s FC Bus or SA Bus. If the IOM is at the 
End-of-Line (EOL) position on the Bus, set the EOL 
switch to the ON position. Otherwise, set the EOL 
switch to the OFF position (Figure 11). The controller 
ships with the EOL switch set in the OFF position.  

Setting the Jumpers

Binary Output INT/EXT Jumpers

The Binary Output jumpers (OUT1 through OUT3) are 
located on the circuit board in the mounting base near 
the binary outputs. These jumpers select whether the 
output provides internal power to the load (INT) or 
requires external power (EXT). See Figure 12.   

When set to the INT position, the IOM controller is the 
power source for the Binary Output and both sides of 
the load can be wired directly to the OUTx and COMx 
terminals.

Setting the jumper to the EXT position isolates the 
Binary Outputs and power must come from one or 
more external sources. Do not wire the load directly to 
the OUTx and COMx terminals. Wire one side of the 
load to the source and the other side of the load to the 
OUTx terminal. Wire the other side of the external 
power source to the COMx terminal.

Analog Input Load Resistor Enable/Disable

The Analog Input Resistor Enable/Disable jumpers 
(J10 through J15) are located on the circuit board in the 
controller cover. These jumpers can permanently 
connect the internal 4-20 mA, 100 ohm load resistor to 
the input terminals. There is one jumper for each of the 
Universal Inputs. See Figure 13.   

Software configuration of the Universal Input normally 
selects the enabling or disabling of the analog input 
load resistor. In cases when the analog input load 
resistor must be left connected even when power is 
OFF to the controller, set this jumper to the ENABLE 
position.

Note:

 This jumper must be in the DISABLE position 

for all Universal Input modes other than 4-20 mA.

IMPORTANT: Do not

 set the Binary Output  

jumpers to INT when an external transformer is 
wired to the Binary Output terminals. Failure to 
follow this precaution may cause damage to the 
controller.

Figure 10: Device Address Switches Set to 21

F

IG

:f

e

c_

di

p_

sw

tc

h

12

8

64

32

16

8

4

2

1

ON

Note:

 Switch 128 is 

used to enable or 
disable an FEC for
wireless operation.

Figure 11: EOL Switch Positions

FI

G

:E

OL_

S

w

tc

h

EOL ON Position

EOL Off Position

O
N

O
N

Figure 12: Binary Output Jumper Positions

Jumper

Pins

Jumper positioned 
on top two pins

Jumper positioned 
on bottom two pins

INT

EXT   (Default)

F

IG

:b

in

_

o

u

t_

jm

p

r

Figure 13: Analog Input Resistor Jumper Positions

Pins

Jumper positioned 
on top two pins

Jumper positioned 
on bottom two pins

ENABLE

DISABLE  (Default)

F

IG

:a

n

lg

_

in

p

t_

jm

p

r

Summary of Contents for IOM4710

Page 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Page 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Page 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Page 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Page 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Page 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Page 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Page 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Page 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Page 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Page 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Page 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Reviews: