IOM4710 Input/Output Module Installation Instructions

11

Technical Specifications

 

 

   

AP-TBK3PW-0

Replacement Power Terminal, 3 Position Connector, Gray, Bulk Pack

MS-BTCVT-1

Wireless Commissioning Converter, with Bluetooth technology

MS-BTCVTCBL-700

Cable replacement set for the MS-BTCVT-1 or the NS-ATV7003-0; includes one 5-foot retractable 
cable

MS-DIS1710-0

Local Controller Display for FEC1610 and FEC2610 models

MS-FUSE01-0 

Replacement fuse, bulk pack

Table 5:  FEC/IOM Accessories (Order Separately) (Part 2 of 2)

Product Code 
Number

Description

IOM4710 Input/Output Module

Product Code Numbers

MS-IOM4710-0 - Cover
MS-IOB4710-0 - Triac Mounting Base
MS-IOU4710-0 - Cover and Triac Mounting Base

Supply Voltage

20-30 VAC at 50 or 60 Hz, Class 2 or Safety Extra Low Voltage (SELV)

Power Consumption

10 VA typical, 14 VA maximum plus all BO and Configurable Output loads

Ambient Conditions

Operating: 

0 to 50°C (32 to 122°F); 10 to 90% RH noncondensing

Storage: 

-40 to 70°C (-40 to 158°F); 10 to 90% RH noncondensing

Terminations

Screw terminals, 3-Position Screw Terminal Pluggable Blocks, 4-Position Screw Terminal 
Pluggable Blocks

Controller Addressing

DIP switch set (4-127). Addresses 1-3, 128-255 are reserved.

Communications Bus

BACnet® MS/TP; 3-wire FC Bus between the NAE/NCE and other devices. 4-wire SA Bus 
when used as expansion to FEC.

1

Analog Input/Analog Output 
Resolution and Accuracy

Analog Input:

 16-bit resolution

Analog Output:

 16-bit resolution and ±200 mV in 0-10 VDC applications

Mounting

On flat surface with screws on three mounting clips or a single 35 mm DIN rail

Dimensions
(Height x Width x Depth)

180 x 127 x 58  (7-1/16 x 5 x 2-1/4 in.)

Housing

Plastic housing
Plastic material: ABS + polycarbonate UL94 5VB
Protection: IP20 (IEC529)

Weight

IOM4710: 

0.68 kg (1.5 lb)

Compliance

United States: 

UL Listed, File E107041, CCN PAZX, UL 916, Energy Management 

Equipment; UL Listed, File S4977, UUKL 864 - 9th Edition, Smoke Control Equipment (MS-
IOMx710-0U and MS-IOU4710-0U models only) 
FCC Compliant to CFR47, Part 15, Subpart B, Class A

Canada: 

UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal 

Equipment; Industry Canada Compliant, ICES-003

Europe: 

CE Mark, EMC Directive 89/336/EEC, in accordance with EN 61000-6-3 (2001) 

Generic Emission Standard for Residential and Light Industry and EN 61000-6-2 (2001) 
Generic Immunity Standard for Heavy Industrial Environment and the Low Voltage Directive 
73/23/EEC in accordance with EN 60730-1 (1999) Automatic electrical controls for 
household and similar use.

Australia and New Zealand:

 C-Tick Mark, Australia/NZ Emissions Compliant

BACnet International: 

BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet 

Application Specific Controller (B-ASC)

1.

For more information, refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products.

Summary of Contents for IOM4710

Page 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Page 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Page 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Page 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Page 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Page 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Page 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Page 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Page 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Page 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Page 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...