Commissioning
Commission the IOM controller through the Wireless
Commissioning Converter with Bluetooth® Technology
(BTCVT) and the Controller Configuration Tool (CCT)
software. Refer to the CCT
Help
.
Troubleshooting
Use Table 4 to troubleshoot the IOM controller.
Replacing the Fuse
If you connect power to the controller, but it does not
function, you may need to replace the fuse. Use the
following procedure to replace the fuse:
1.
Remove power from the controller.
2.
Loosen the cover screw and remove the cover.
3.
Remove the fuse. See Figure 14.
4.
Install a new replacement fuse.
5.
Replace the cover. See
6.
Reconnect power to the controller.
Repair Information
If the IOM controller fails to operate within its
specifications, replace the unit. For a replacement IOM
controller, contact the nearest Johnson Controls®
representative.
Accessories
Use Table 5 to order accessories for the IOM controller.
Location
of
Removable
Fuse
F
IG
:f
se
_
rm
v
F
1
Controller Mounting Base
Figure 14: Location of Removable Fuse
Table 4: Status Light-Emitting Diodes (LEDs)
Name
Color
Normal
Descriptions
Power
Green
On Steady
Off Steady = No Power
On Steady = Power is supplied by primary voltage.
Fault
Red
Off Steady
Blink - 2 Hz = Download or startup in progress, not ready for normal operation
Off Steady = No faults
On Steady = Device fault or no application loaded
SA/FC Bus
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
Table 5: FEC/IOM Accessories (Order Separately) (Part 1 of 2)
Product Code
Number
Description
Y64T15-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 30 in. Primary
Leads and 30 in. Secondary Leads, Class 2
Y65A13-0
Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AS], 8 in. Primary
Leads and 30 in. Secondary Leads, Class 2
Y65T42-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount [Y65SP+], 8 in.
Primary Leads and Secondary Screw Terminals, Class 2
Y65T31-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AR+],
8 in. Primary Leads and Secondary Screw Terminals, Class 2
AP-TBK1002-0
2-position Screw Terminal that Plugs onto VMA output point Spade Lugs
AP-TBK1003-0
3-position Screw Terminal that Plugs onto VMA output point Spade Lugs
AP-TBK4SA-0
Replacement MS/TP SA Bus Terminal, 4 Position Connector, Brown, Bulk Pack
AP-TBK4FC-0