IOM4710 Input/Output Module Installation Instructions

10

Commissioning

Commission the IOM controller through the Wireless 
Commissioning Converter with Bluetooth® Technology 
(BTCVT) and the Controller Configuration Tool (CCT) 
software. Refer to the CCT 

Help

.

Troubleshooting

Use Table 4 to troubleshoot the IOM controller.

Replacing the Fuse

If you connect power to the controller, but it does not 
function, you may need to replace the fuse. Use the 
following procedure to replace the fuse:

1.

Remove power from the controller.

2.

Loosen the cover screw and remove the cover.

3.

Remove the fuse. See Figure 14.

4.

Install a new replacement fuse.

5.

Replace the cover. Se

Attaching the Cover

.

6.

Reconnect power to the controller.

Repair Information

If the IOM controller fails to operate within its 
specifications, replace the unit. For a replacement IOM 
controller, contact the nearest Johnson Controls® 
representative. 

Accessories

Use Table 5 to order accessories for the IOM controller.  

Location

of 

Removable 

Fuse

F

IG

:f

se

_

rm

v

F

1

Controller Mounting Base

Figure 14: Location of Removable Fuse

Table 4:  Status Light-Emitting Diodes (LEDs)

Name

Color

Normal

Descriptions

Power

Green

On Steady

Off Steady = No Power
On Steady = Power is supplied by primary voltage.

Fault

Red

Off Steady

Blink - 2 Hz = Download or startup in progress, not ready for normal operation
Off Steady = No faults
On Steady = Device fault or no application loaded

SA/FC Bus

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring

Table 5:  FEC/IOM Accessories (Order Separately) (Part 1 of 2)

Product Code 
Number

Description

Y64T15-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 30 in. Primary 
Leads and 30 in. Secondary Leads, Class 2

Y65A13-0

Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AS], 8 in. Primary 
Leads and 30 in. Secondary Leads, Class 2

Y65T42-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount [Y65SP+], 8 in. 
Primary Leads and Secondary Screw Terminals, Class 2

Y65T31-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount [Y65AR+], 
8 in. Primary Leads and Secondary Screw Terminals, Class 2

AP-TBK1002-0

2-position Screw Terminal that Plugs onto VMA output point Spade Lugs

AP-TBK1003-0

3-position Screw Terminal that Plugs onto VMA output point Spade Lugs

AP-TBK4SA-0

Replacement MS/TP SA Bus Terminal, 4 Position Connector, Brown, Bulk Pack

AP-TBK4FC-0

Replacement MS/TP FC Bus Terminal, 4 Position Connector, Blue, Bulk Pack

Summary of Contents for IOM4710

Page 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Page 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Page 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Page 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Page 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Page 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Page 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Page 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Page 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Page 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Page 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Page 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Reviews: