Johnson Controls Frick XL Installation Operation & Maintenance Download Page 14

XL EVAPORATIVE COOLING PRODUCTS

MAINTENANCE

S140-600 IOM (NOV 07)
Page 14

will promote belt wear and increase turnover.  Groove gauges 
are also available to make it easy to see if the grooves are 
worn. If more than 1/32” of wear can be seen, the sheave 
should be replaced.

Alignment of sheaves is extremely important for proper belt 
installation. The sheaves are aligned at the factory, but should 
be rechecked when new belts are installed. Use a straight 
edge to check alignment. Misalignment will show up as a gap 
between the outside face and the straight edge. Two condi-
tions for misalignment exist, angular and parallel. To check 
both parallel and angular alignment, refer to the Figure 14 
below and follow these instructions:

1.

 While placing a straight edge across the top of both motor 

and fan sheaves, check for four points of contact.

2.

 If a four-point contact is achieved, skip to the belt tension-

ing section.

3. 

To adjust for parallel misalignment, adjust the motor or 

fan shaft sheave.

4. 

To adjust for angular misalignment, adjust the motor mount 

adjustment nuts. This should also be done when tensioning 
the belt.

Figure 14 - Sheave Alignment

Belt Replacement

When the decision is made to replace the belt, follow these 
steps:

1.

 Lock and tag out the starter.

2.

 After the power has been turned off and the motor guard 

removed, loosen the motor mount adjustment nuts.

3.

 Move the motor until there is enough slack in the belt so 

it can be removed without prying.

4. 

Remove the old belts and inspect for unusual wear. Exces-

sive wear may indicate problems with alignment or sheave 
damage.

5.

 Order replacement belts from the factory to ensure a 

proper belt equivalent.

6.

 Inspect other drive components such as bearings and 

sheaves for alignment, wear, lubrication, etc.

7.

 Clean the sheaves of debris before installing the new 

belt.

8

. Install the new belts, align the drive, and tension the belts 

according to the procedures outlined here.

Belt Tensioning

Proper tension of a belt is very important to ensure maximum 
belt life. If too little tension is applied, the belt will slip.  Too 
much tension can reduce belt and bearing life. It is not recom-
mended that belt dressing is used when belt slippage occurs 
as this will damage the belt and cause premature failure.

1. 

Decrease the center distance between the sheaves so 

that the sheaves are somewhat loose.

2.

 Arrange the belts so the top and bottom spans have the 

same amount of sag. On vertical drives, arrange the belts so 
that each side has about the same amount of slack.

3.

 Apply tension to the belts by increasing the center distance 

between the sheaves until the belts are snug.

4.

 Operate the drive a few minutes to seat the belts in the 

sheave grooves. Observe the operation of the drive during 
start-up. A slight bowing of the slack side of the drive indi-
cates proper tension. If the slack side remains taut during the 
peak load, the drive is to tight. Excessive bowing or slippage 
indicates insuffi cient tension. If the belts squeal as the motor 
comes on, they are not tight enough. The drive should be 
stopped and the belts tightened.

NOTE: Do not overtighten the drive. 

If the above procedure 

still results in the belts squealing, but the belts are still taut 
on the slack side, a more precise method of testing the belt 
tension must be used. In this case, use a belt tensioning gage 
available from V-belt drive manufacturers or from factory.

New Belt Run-In

During initial startup of new belts, a belt run-in procedure is 
recommended. During start-up, follow these instructions:

1. 

During start-up, look and listen for unusual noise or vibra-

tion.  

2.

 After shutting down and locking out the starter, check the 

bearings and motor. If they feel hot, the belt tension may be 
too tight.

3.

 Run the drive under full load for 24 hours of continuous 

operation. Running the belts under full load allows them to 
seat themselves into the grooves.

4.

 After running the drive, check the tension of the belts.  

Retension to the recommended values.

This run-in procedure will reduce the future need for re-ten-
sioning and will help extend the life of the belts.

Summary of Contents for Frick XL

Page 1: ...XL EVAPORATIVE COOLING PRODUCTS Form S140 600 IOM NOV 2007 INSTALLATION OPERATION MAINTENANCE File SERVICE MANUAL Section 140 Replaces S140 600 NOV 2005 Dist 3 3a 3b 3c ...

Page 2: ...LC Spray Header Nozzle Orientation 13 Figure 13 XLP Spray Header Nozzle Orientation 13 Figure 14 Sheave Alignment 14 TABLES Table 1 XLC Foundation Layout Dimensions 5 Table 2 XLP Foundation Layout Dimensions 7 Table 3 Rigging Cable Lengths 8 NOTE Installation operation maintenance and repair of this equipment should only be accomplished by qualified person nel Failure to follow this note may resul...

Page 3: ...ack aged and usually placed inside the pan section Mastic Bolts Nuts Washers and any accessory items TRANSIT DAMAGE CLAIMS All claims must be made by the consignee This is an ICC requirement Request immediate inspection by the agent of the carrier and be sure the proper forms are executed Contact Parts and Warranty Department to report damage or shortage claims UNIT IDENTIFICATION NOTE When inquir...

Page 4: ...temperature falls below 40 F 4 4 C Water Chemistry All evaporative cooled condensers op erate on principles that encourage biological growth in the recirculating water unless effective treatment is applied Re circulating water must be periodically analyzed for biological culture plate counts XL units should not be operated without an effective biological treatment program NOTE Emergency shock trea...

Page 5: ...epresents the center lines of the mounting holes in the unit The dashed lines show the location of the structural beams to which the unit is mounted XLC CENTRIFUGAL FAN UNITS XLC units are shipped in two pieces the pan coil section and the fan section The first step of the installation is to mount the pan coil section on the structural beams and bolt it to the beams The rigging of the two pieces i...

Page 6: ...l mounting flanges are touching Figure 4b 4 On each blower install bolts with a flat washer under both the bolt and nut 5 Tighten all bolts connecting fan and pan coil Sections together before removing rigging 6 Align the V belt drive and check tension in the belts using the procedures in the section labeled Fan Drives and Belts in this manual 7 Replace all guards and the motor hood access panel N...

Page 7: ...eams with bolts The rigging of the two pieces is shown in Figures 7a through 7c For cable lengths see Table 3 Figure 7a XLP Fan Section Rigging All models except 1570 2 and 1660 2 through 1880 2 Figure 7b XLP Fan Section Rigging Models 1570 2 and 1660 2 through 1880 2 MODEL A B C D E F S90 thru S175 S185 S190 S200 S205 145 141 57 5 1 625 0 75 S180 S195 S210 thru S270 145 141 68 5 M155 thru M280 12...

Page 8: ... 7c Use drift pins in bolt holes to ensure proper alignment See Figure 8 NOTES 1 Use spreaders and blocking to protect casing from possible damage caused by slings 2 Remove eliminator tie straps and eliminators as nec essary to access lifters 3 Mount coil connection toward access door unless specified differently on product drawing 4 When provided mount desuperheater on top of unit using the holes...

Page 9: ...annel can be removed by hand It will be necessary to alternate between isolators in order to uniformly raise the unit Do not attempt to place all the weight on any one isolator but distribute the load proportionally 9 After the unit is level tighten the vertical restraining nuts finger tight then back off one half turn Lock each nut with the jam nuts provided Figure 9 Vibration Isolator Feet ISOLA...

Page 10: ...ance Manual for new belt run in procedures 3 BREAKING IN THE GALVANIZED SURFACES A proper break in procedure should be followed for water treatment to allow the galvanized surfaces to break in or passivate This allows the galvanized surfaces to form a self protecting zinc carbonate layer A qualified water treat ment specialist can provide specific details but following are some guidelines Clean al...

Page 11: ...ntrol and freeze protection A common application for Vane Axial units is to cycle the operating fans to achieve capacity control Typically the fans are cycled off as capacity drops and finally the pump is shut off In cold weather operation Frick recommends that the pump should be the first item shut off to achieve capacity control By running the unit dry in cold applications the unit s drive is pr...

Page 12: ...mended that the chemical feed for acid treatment be done in a tank such as a remote sump tank that allows complete diffusion of the chemical before it is pumped to the unit In addition to the chemical feed controls regular inspections of feed valve and chemical levels should be included in the preventative maintenance plan to avoid chemical concentration of the water outside of the accept able ran...

Page 13: ...The coil should be examined monthly for signs of scale buildup and any obstructions between the tubes should be removed If there is evidence of scale buildup on the coil check the bleed valve for adequate bleed off If the bleed off valve is functioning properly contact your local water treat ment company for recommendations FAN MOTOR AND SPRAY PUMP MOTOR The motors should be checked and or lubrica...

Page 14: ...ning Proper tension of a belt is very important to ensure maximum belt life If too little tension is applied the belt will slip Too much tension can reduce belt and bearing life It is not recom mended that belt dressing is used when belt slippage occurs as this will damage the belt and cause premature failure 1 Decrease the center distance between the sheaves so that the sheaves are somewhat loose...

Page 15: ...e float is approximately 1 0 to 1 5 below the centerline of the overflow 11 Start spray pump and check for the proper rotation as indicated by sticker on pump motor On Remote installations where the unit pump was not furnished by the factory a globe valve should be installed in the pump discharge line and the pump flow rate adjusted to the correct water flow 12 Inspect spray nozzles and heat trans...

Page 16: ...ews X X X Lubricate the fan and pump motors X Check fan for rotation without obstruction X X Check fan and pump motor for proper rotation X Drain sump and piping X Inspect protective finish X X Lubricate capacity control and or discharge X X X closure damper bearings and working joints Inspect adjust damper linkage X X X Inspect electric pan water level control X X X stilling chamber SAFETY Adequa...

Page 17: ...____________________________ One Set FAN BUSHING ________________________________________________ One Set MOTOR BUSHING _____________________________________________ One Set FAN SHEAVE _________________________________________________ One Set MOTOR SHEAVE ______________________________________________ One Set FLOAT VALVE ASSEMBLY _______________________________________ One SPRAY NOZZLES __________...

Page 18: ...XL EVAPORATIVE COOLING PRODUCTS NOTES S140 600 IOM NOV 07 Page 18 ...

Page 19: ...XL EVAPORATIVE COOLING PRODUCTS NOTES S140 600 IOM NOV 07 Page 19 ...

Page 20: ...DF1 and Modbus RTU I Q NET connects for local or remote access I Q NET can be applied to both new and existing systems I Q NET means precise control 24 hours a day seven days a week I Q NET distributed architecture mean faster easier economical installations I Q NET delivers increased operating efficiency and lowers energy costs Available on Frick screw compressors condensers evaporators AcuAir hy...

Reviews: