Example 3
What are the High Motor Amp setpoints if a 305 HP Vyper is
to drive a motor with 1.00 SF and a 340 Amp FLA? Using
the Values, determine whether Table A or Table B should be
used to calculate the setpoints.
SF 1.00 motors need to be derated by dividing the Nameplate
FLA by 1.15 for an Applied motor FLA. Therefore:
340 A / 1.15 = 295 A
Line
Parameter
Value
1
Applied Motor FLA
295 A
2
Applied Service Factor
1.15
3
Multiply (Line 1 x Line 2)
340 A
4
HP rating of Vyper Drive
305 HP
5
Vyper Amp Limit
If Line 4 is 305/254 HP, value is 380 A
If Line 4 is 437/362 HP, value is 565 A
380 A
6
Multiply Line 5 x 1.05
399 A
The Line 3 value of 340 Amps is less than the Line 6 Value
of 399 Amps. Therefore, use Table A for the calculation.
Table A
Parameter
Equation
Value
Load Inhibit
=Applied Motor FLA x 1.1
324 A
Force Unload
=Applied Motor FLA x 1.12
330 A
Warning
=Applied Motor FLA x 1.13
333 A
Shutdown
=Applied Mtr. FLA x 1.15
339 A
High Motor Amps
Load Inhibit
310
Force Unload
324
Delay
Warning
330
5 SEC
Shutdown
337
5 SEC
Example 4
What are the High Motor Amp setpoints if a 437 HP Vyper
™
is to drive a motor with 1.00 SF and a 552 A FLA? Using
the Values, determine whether Table A or Table B should be
used to calculate the setpoints.
SF 1.00 motors need to be derated by dividing the Nameplate
FLA by 1.15 for an Applied FLA. Therefore:
552 A / 1.15 = 480 A
Line
Parameter
Value
1
Applied Motor FLA
480 A
2
Applied Service Factor
1.15
3
Multiply (Line 1 x Line 2)
552 A
4
HP rating of Vyper Drive
437 HP
5
Vyper Amp Limit
If Line 4 is 305/254 HP, value is 380 A
If Line 4 is 437/362 HP, value is 565 A
565 A
6
Multiply Line 5 x 1.05
593 A
The Line 3 value of 552 Amps is now less than the Line 6 value
of 593 Amps. Therefore, use Table A for the calculation.
Table A
Parameter
Equation
Value
Load Inhibit
=Applied Motor FLA x 1.1
528 A
Force Unload
=Applied Motor FLA x 1.12
537 A
Warning
=Applied Motor FLA x 1.13
542 A
Shutdown
=Applied Mtr. FLA x 1.15
552 A
High Motor Amps
Load Inhibit
504
Force Unload
528
Delay
Warning
538
5 SEC
Shutdown
549
5 SEC