background image

FRICK

®

 QUANTUM

 LX/HD RETROFIT

INSTALLATION INSTRUCTIONS

090.040-I (MAR 2012)

Page 9

generated between the VFD output and the motor, relative 
to a conventional starter. If these grounds are left coupled 
by a common back-plate in the starter/drive, this noise can 
be direct coupled to the control power, analog device, and 
communications  grounding  and  may  cause  unexplained 
behavior and possible damage to components. 

To install correctly, run a separate, properly sized (typically 10 
or 8 AWG) insulated wire to ground along with the 3-phase 
ground to the 3-phase supply transformer (plant). This will 
require  that  the  3-phase  ground  and  the  control  power 
ground be electrically isolated except for the connection at 
the plant supply transformer. 

This  style  of  grounding  should  steer  the  noise  (EMI/RFI) 
to earth ground, reducing the potential for it to affect the 
sensitive  equipment,  which  could  occur  if  the  grounds 
were  left  coupled. 

NOTE:  If  all  other  recommendations 

for grounding are followed, this process should not be 
necessary.

CONDUIT

All national and local codes must be followed for conduit 
with regard to materials, spacing and grounding. In addition, 

Johnson  Controls-Frick  requirements  must  be  followed 
where  they  exceed  or  match  national  or  local  codes. 
Conversely, there is no allowance for any practices that are 
substandard to what is required by national or local codes.

 

Johnson Controls-Frick conduit requirements:

  For 

variable frequency drives

 (VFDs) of any type, threaded 

metallic  or  threaded  PVC-coated  metallic  is  required 
for both the power feed (line side) from the source and 
between the VFD output and the motor (load side).

  Regardless  of  horsepower,  both  the  incoming  3-phase 

power to the drive input terminals and the outgoing PWM 
(pulse width modulated) power from the output terminals 
of the drive to the motor will be run in separate conduits 
that will be grounded.

  Under no circumstances regardless of horsepower, will the 

incoming 3-phase power to the drive be mixed or ran in 
the same conduit, wire duct or any other style of enclosure 
with the outgoing PWM power from the drive output to 
the motor.

  PVC conduit is acceptable 

only

 when 

VFD rated cable

 of 

the proper conductor size and ground is used. This applies 
to both the line side and load side of the drive. When VFD 
rated  cable  is  not  used,  threaded  metallic  or  threaded 
PVC-coated metallic must be used. 

  When threaded metallic or threaded PVC-coated metallic 

is used, it must be grounded at both ends. 

  When  not  required  to  be  in  metal  or  other  material  by 

national  or  local  codes,  conduits  for  the  power  feed 
(3-phase) of constant speed starters may be PVC. 

  When  not  required  to  be  in  metal  or  other  material  by 

national or local codes, conduits between a constant speed 
starter and the motor (3-phase) may be PVC. 

  Any  unshielded  control  voltage,  signal,  analog,  or 

communication wiring that does not maintain 12 inches 
of separation from any 3-phase conductors for every 33 

feet (10 meters) of parallel run must be in metal conduit 
which will be grounded. 

Separation: (0-33 feet, 0-10 meters – 12 inches, .3 meters), 

(33-66 feet, 10-20 meters – 24 inches, .6 meters) 

  Since PVC conduit does absolutely nothing to protect lower 

voltage  lines  from  the  magnetic  field  effects  of  higher 
voltage conductors, running either the lower or the higher 
voltage lines in PVC, does not reduce these requirements 
on separation. Only running in metal conduit can relieve 
these requirements. 

  Due to the level of EMI that can be induced onto lower 

voltage lines when running multiple feeders in a trench, 
control power, communications, analog, or signal wiring 
cannot be run in trenches that house multiple conduits/
electrical ducts carrying 3-phase power to starters/vfd or 
motors. 

  Control power, communications, analog, or signal wiring 

should be run overhead (preferred) or in a separate trench. 
If these lines are not in threaded metallic or threaded PVC-
coated metallic, abiding by the separation requirements 
noted above is necessary.

  Though not recommended, if cable trays are used, 

metallic 

dividers  must  be  used  for  separation  of  conductors  of 
unlike voltages and types (AC or DC).

NOTE: When in doubt contact the factory or use threaded 
metallic or threaded PVC coated metallic conduit.

WIRING PRACTICES 

Do not mix wires of different voltages in the same conduit. 
An  example  of  this  would  be  the  installation  of  a  screw 
compressor package where the motor voltage is 480 volts 
and the electronic control panel power is 120 volts. The 480 
volt circuit must be run from the motor starter to the motor 
in its own conduit. The 120 volt circuit must be run from the 
motor starter control transformer to the electronic control 
panel in its own separate conduit. If the two circuits are run 
in the same conduit, transients on the 480 volt circuit will be 
induced onto the 120 volt circuit causing functional problems 
with the electronic control panel. Metallic dividers must be 
used in wire way systems (conduit trays) to separate unlike 
voltages. The same rule applies for 120 volt wires and 220 
volt wires. Also, never run low voltage wires for DC analog 
devices or serial communications in the same conduit with 
any AC wiring including 120 volt wires. See Figure 4.

Figure 4

Summary of Contents for FRICK QUANTUM LX/HD

Page 1: ...UM LX HD CONTROL INSTALLATION INSTRUCTIONS Form 090 040 I MAR 2012 INSTALLATION File SERVICE MANUAL Section 90 Replaces S90 130 I OCT 2004 Dist 3 3a 3b 3c Please check www johnsoncontrols com frick for the latest version of this publication ...

Page 2: ...RIAL RECEIVED FOR SUITABILITY AND COMPLETENESS Instructions are provided for retrofit conversion from either RWB Electromechanical or RWB II Microprocessor Control to QUANTUM LX HD Control Other screw compressors not manufactured by Frick can also be converted to the QUANTUM LX HD Control Frick screw compressor pack ages where the compressor itself was not manufactured by Frick are considered to b...

Page 3: ... con nection available and will require cutting a hole and welding in a connection for the temperature well Seal all threaded connections to prevent leaks 10 Place silicone heat transfer compound on the tip of the temperature probes and install them in the temperature wells 11 Run separate electrical conduit between the control panel and the temperature probe electrical boxes DO NOT RUN THE TEMPER...

Page 4: ...om the junction box to the QUANTUM LX HD enclosure is to use the number 12 gauge blue and black wires which were used for common and 5VDC The most common electronic control panel problems are due to undersized AC power wiring poor grounds and control power supplied from lighting panels that have other devices tied to them that generate large amounts of AC line noise Please follow these directions ...

Page 5: ...e temperature probe from the well Place the temperature probe in a container of water along with a quality test thermometer 42 Wait for approximately two minutes and compare the thermometer reading with the temperature probe reading Enter in the correction for temperature if required 43 Step to the next temperature to be calibrated and locate the associated temperature probe on the compressor pack...

Page 6: ...UCTIONS 090 040 I MAR 2012 Page 6 TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB II TO QUANTUM HD CONTROL TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB AND OTHER MANUFACTURER S UNITS TO QUANTUM HD CONTROL QUANTUM LX HD PANEL QUANTUM LX HD PANEL ...

Page 7: ...y sizing control wires and other wiring specifications Throughout this document the term Electronic Control Panel is used to refer to the microprocessor mounted on the com pressor package or a Central Control System panel It is very important to read the installation instructions thoroughly before beginning the project Make sure you have drawings and instructions with your equipment If not call th...

Page 8: ...the three phase power wiring This must be sized in accordance to the NEC and any local codes relative to the highest rated circuit overload protection provided in the circuit The manufacturer may require a larger ground conductor than what is required by the NEC for proper steering of EMI from sensitive circuits This conductor must also be insulated to avoid inadvertent contact at multiple points ...

Page 9: ... in metal or other material by national or local codes conduits for the power feed 3 phase of constant speed starters may be PVC When not required to be in metal or other material by national or local codes conduits between a constant speed starter and the motor 3 phase may be PVC Any unshielded control voltage signal analog or communication wiring that does not maintain 12 inches of separation fr...

Page 10: ...using catastrophic failure Route the conduit to the sides or bottom of the panel and use a conduit drain If the conduit must be routed to the top of the panel use a sealable conduit fitting which is poured with a sealer after the wires have been pulled terminated and the control functions have been checked A conduit entering the top of the enclosure must have a NEMA 4 hub type fitting between the ...

Page 11: ...em providing shutdown protection for a Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter contactor still energized the compres sor auxiliary will continue to feed an okay signal to the Quantum LX panel This may allow the motor to be subjected to the fault condition on the 3 pha...

Page 12: ...ohnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 090 040 I 2012 03 Supersedes S90 130 I 2004 10 Subject to change without notice Published in USA 0812 GUI 50 2012 Johnson Controls Inc ALL RIGHTS RESERVED ...

Reviews: