background image

FRICK

®

 QUANTUM

LX/HD RETROFIT

INSTALLATION INSTRUCTIONS

090.040-I (MAR 2012)

Page 10

Never run any wires through an electronic control panel 
that do not relate to the function of the panel

. Electronic 

control panels should never be used as a junction box.  These 
wires may be carrying large transients that will interfere with 
the operation of the control panel. An extreme example of 
this would be to run 480 volts from the starter through the 
electronic control panel to an oil pump motor.

When running conduit to the electronic control panel, use 
the access holes (knockouts) provided by the manufacturer. 
These holes are strategically placed so that the field wiring 
does not interfere with the electronics in the panel. Never 
allow field wiring to come in close proximity with the con-
troller boards since this will almost always cause problems.

Do not drill into an electronic control panel to locate conduit 
connections. You are probably not entering the panel where 
the manufacturer would like you to since most manufactur-
ers recommend or provide prepunched conduit connections.  
You may also be negating the NEMA rating of the enclosure. 
Drilling can cause metal filings to land on the electronics and 
create a short circuit when powered is applied. If you must 
drill the panel, take the following precautions: 

•  First, call the panel manufacturer before drilling into the 

panel to be sure you are entering the panel at the right 
place. 

•  Take measures to avoid ESD (electrostatic discharge) to the 

electronics as you prep the inside of the Electronic control 
panel. This can be done by employing an antistatic wrist 
band and mat connected to ground. 

•  Cover the electronics with plastic and secure it with mask-

ing or electrical tape. 

•  Place masking tape or duct tape on the inside of the panel 

where you are going to drill. The tape will catch most of 
the filings. 

•  Clean all of the remaining filings from the panel before 

removing the protective plastic. 

When  routing  conduit  to  the  top  of  an  electronic  control 
panel, condensation must be taken into consideration. Water 
can condense in the conduit and run into the panel causing 
catastrophic failure. Route the conduit to the sides or bottom 
of the panel and use a conduit drain. If the conduit must be 
routed to the top of the panel, use a sealable conduit fitting 
which  is  poured  with  a  sealer  after  the  wires  have  been 
pulled,  terminated,  and  the  control  functions  have  been 
checked. A conduit entering the top of the enclosure must 
have a NEMA-4 hub type fitting between the conduit and 
the enclosure so that if water gets on top of the enclosure 
it cannot run in between the conduit and the enclosure. This 
is extremely important in outdoor applications.

NOTE: It is simply NEVER a good practice to enter through 
the top of an electronic control panel or starter panel that 
does not already have knockouts provided. If knockouts 
are not provided for this purpose it is obvious this is not 
recommended and could VOID WARRANTY. 

Never add relays, starters, timers, transformers, etc. in-
side an electronic control panel without first contacting 
the  manufacturer.

  Contact  arcing  and  EMI  emitted  from 

these devices can interfere with the electronics. Relays and 
timers are routinely added to electronic control panels by the 
manufacturer, but the manufacturer knows the acceptable 

device  types  and  proper  placement  in  the  panel  that  will 
keep interference to a minimum. If you need to add these 
devices,  contact  the  manufacturer  for  the  proper  device 
types and placement.   

Never run refrigerant tubing inside an electronic control 
panel. 

If the refrigerant is ammonia, a leak will totally destroy 

the electronics.

If the electronic control panel has a starter built into the 
same panel, be sure to run the higher voltage wires where 
indicated  by  the  manufacturer.

  EMI  from  the  wires  can 

interfere with the electronics if run too close to the circuitry.

Never daisy-chain or parallel-connect power or ground 
wires to electronic control panels.

 Each electronic control 

panel must have its own control power supply and ground 
wires back to the power source (Plant Transformer). Multiple 
electronic control panels on the same power wires create 
current surges in the supply wires, which may cause control-
ler malfunctions. Daisy-chaining ground wires, taking them 
to ground at each device, allows ground loop currents to 
flow between electronic control panels which also causes 
malfunctions. See Figure 5.

Figure 5

Summary of Contents for FRICK QUANTUM LX/HD

Page 1: ...UM LX HD CONTROL INSTALLATION INSTRUCTIONS Form 090 040 I MAR 2012 INSTALLATION File SERVICE MANUAL Section 90 Replaces S90 130 I OCT 2004 Dist 3 3a 3b 3c Please check www johnsoncontrols com frick for the latest version of this publication ...

Page 2: ...RIAL RECEIVED FOR SUITABILITY AND COMPLETENESS Instructions are provided for retrofit conversion from either RWB Electromechanical or RWB II Microprocessor Control to QUANTUM LX HD Control Other screw compressors not manufactured by Frick can also be converted to the QUANTUM LX HD Control Frick screw compressor pack ages where the compressor itself was not manufactured by Frick are considered to b...

Page 3: ... con nection available and will require cutting a hole and welding in a connection for the temperature well Seal all threaded connections to prevent leaks 10 Place silicone heat transfer compound on the tip of the temperature probes and install them in the temperature wells 11 Run separate electrical conduit between the control panel and the temperature probe electrical boxes DO NOT RUN THE TEMPER...

Page 4: ...om the junction box to the QUANTUM LX HD enclosure is to use the number 12 gauge blue and black wires which were used for common and 5VDC The most common electronic control panel problems are due to undersized AC power wiring poor grounds and control power supplied from lighting panels that have other devices tied to them that generate large amounts of AC line noise Please follow these directions ...

Page 5: ...e temperature probe from the well Place the temperature probe in a container of water along with a quality test thermometer 42 Wait for approximately two minutes and compare the thermometer reading with the temperature probe reading Enter in the correction for temperature if required 43 Step to the next temperature to be calibrated and locate the associated temperature probe on the compressor pack...

Page 6: ...UCTIONS 090 040 I MAR 2012 Page 6 TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB II TO QUANTUM HD CONTROL TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB AND OTHER MANUFACTURER S UNITS TO QUANTUM HD CONTROL QUANTUM LX HD PANEL QUANTUM LX HD PANEL ...

Page 7: ...y sizing control wires and other wiring specifications Throughout this document the term Electronic Control Panel is used to refer to the microprocessor mounted on the com pressor package or a Central Control System panel It is very important to read the installation instructions thoroughly before beginning the project Make sure you have drawings and instructions with your equipment If not call th...

Page 8: ...the three phase power wiring This must be sized in accordance to the NEC and any local codes relative to the highest rated circuit overload protection provided in the circuit The manufacturer may require a larger ground conductor than what is required by the NEC for proper steering of EMI from sensitive circuits This conductor must also be insulated to avoid inadvertent contact at multiple points ...

Page 9: ... in metal or other material by national or local codes conduits for the power feed 3 phase of constant speed starters may be PVC When not required to be in metal or other material by national or local codes conduits between a constant speed starter and the motor 3 phase may be PVC Any unshielded control voltage signal analog or communication wiring that does not maintain 12 inches of separation fr...

Page 10: ...using catastrophic failure Route the conduit to the sides or bottom of the panel and use a conduit drain If the conduit must be routed to the top of the panel use a sealable conduit fitting which is poured with a sealer after the wires have been pulled terminated and the control functions have been checked A conduit entering the top of the enclosure must have a NEMA 4 hub type fitting between the ...

Page 11: ...em providing shutdown protection for a Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter contactor still energized the compres sor auxiliary will continue to feed an okay signal to the Quantum LX panel This may allow the motor to be subjected to the fault condition on the 3 pha...

Page 12: ...ohnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 090 040 I 2012 03 Supersedes S90 130 I 2004 10 Subject to change without notice Published in USA 0812 GUI 50 2012 Johnson Controls Inc ALL RIGHTS RESERVED ...

Reviews: