background image

FRICK

®

 QUANTUM

LX/HD RETROFIT

INSTALLATION INSTRUCTIONS

090.040-I (MAR 2012)

Page 8

are common to a circuit. EMI cannot travel easily through 
transformers  and  therefore  can  be  isolated  from  selected 
circuits. Use a control power transformer of the proper VA 
rating, usually provided in the compressor drive motor starter, 
to isolate the electronic control panel from other equipment 
in the plant that generate EMI. See Figure 1.

GROUNDING

Grounding is the most important factor for successful opera-
tion and is typically the most overlooked.  The NEC states that 
control equipment may be grounded by using the rigid conduit 
as a conductor. This worked for the earlier relay systems, but 
it is in no way acceptable for electronic control equipment. 
Conduit is made of steel and is a poor conductor relative 
to an insulated stranded copper wire. Electronic equipment 
reacts to very small currents and must have a proper ground 
in  order  to  operate  properly;  therefore,  stranded  copper 
grounds are required for proper operation. 

For proper operation, the control power ground circuit must 
be a single continuous circuit of the proper sized insulated 
stranded conductor, from the electronic control panel to the 
plant supply transformer (Figure 2). Driving a ground stake 
at the electronic control may also cause additional problems 
since other equipment in the plant on the same circuits may 
ground themselves to the ground stake causing large ground 
flow at the electronic control panel. Also, running multiple 
ground  conductors  into  the  electronic  control  panel  from 
various locations can create multiple potentials resulting in 
ground loop currents. A single ground wire (10 AWG or 8 
AWG) from the electronic control panel, that is bonded to the 
control power neutral at the secondary side of the control 
power transformer in the starter and then to the 3-phase 
ground point, will yield the best results.

Figure 2

NOTE:  Structural  grounding  can  also  result  in  multiple 
ground potentials and is also a relatively poor conductor. 
Therefore, this is not an acceptable method for proper 
operation of electronic equipment.

There must be a ground for the three-phase power wiring. 
This must be sized in accordance to the NEC and any local 
codes relative to the highest rated circuit overload protection 
provided in the circuit. The manufacturer may require a larger 
ground conductor than what is required by the NEC for proper 
steering of EMI from sensitive circuits. This conductor must 

also  be  insulated  to  avoid  inadvertent  contact  at  multiple 
points to ground, which could create Ground Loops. In many 
installations  that  are  having  electronic  control  problems, 
this  essential  wire  is  usually  missing,  is  not  insulated,  or 
improperly sized. 

NEC size ratings are for safety purposes and not necessarily 
for adequate relaying of noise (EMI) to earth ground to avoid 
possible  interference  with  sensitive  equipment.  Therefore 
sizing this conductor 1 – 2 sizes larger than required by code 
will provide better transfer of this noise. 

Johnson Controls-Frick

®

 requires that the ground conductor 

meet the following:: 
•  Stranded Copper
•  Insulated
•  One size larger than NEC requirements for conventional 

starters

•  Two sizes larger than NEC requirements for VFD starters
•  Conduit must be grounded at each end
•  This circuit must be complete from the motor to the starter 

continuing in a seamless manner back to the plant supply 
transformer (power source). 

For Direct Coupled, Package Mounted Starters, the ground 
between the motor and the starter may need to be made 
externally  (Figure  3).  The  connection  on  the  starter  end 
must  be  on  the  starter  side  of  the  vibration  isolators.  Be 
certain the connection is metal to metal. Paint may need 
to  be  removed  to  ensure  a  proper  conductive  circuit. 
The  use  of  counter-sunk  star  washers  at  the  point  of 
connection at each end will maximize metal to metal contact.

Figure 3

VFD Applications

The primary ground conductor that accompanies the three-
phase supply must be stranded copper, insulated and two 
sizes larger than the minimum required by the NEC or any 
other applicable codes. This is necessary due to the increased 
generation of EMI which is a characteristic of a VFD output 
to the motor when compared to a conventional starter. 

For VFD applications, isolation of the control power, analog 
devices,  and  communications  ground  from  the  3-phase 
ground within the starter and the electronic control panel may 
be necessary. This is due to the higher noise (RFI/EMI) levels 

Summary of Contents for FRICK QUANTUM LX/HD

Page 1: ...UM LX HD CONTROL INSTALLATION INSTRUCTIONS Form 090 040 I MAR 2012 INSTALLATION File SERVICE MANUAL Section 90 Replaces S90 130 I OCT 2004 Dist 3 3a 3b 3c Please check www johnsoncontrols com frick for the latest version of this publication ...

Page 2: ...RIAL RECEIVED FOR SUITABILITY AND COMPLETENESS Instructions are provided for retrofit conversion from either RWB Electromechanical or RWB II Microprocessor Control to QUANTUM LX HD Control Other screw compressors not manufactured by Frick can also be converted to the QUANTUM LX HD Control Frick screw compressor pack ages where the compressor itself was not manufactured by Frick are considered to b...

Page 3: ... con nection available and will require cutting a hole and welding in a connection for the temperature well Seal all threaded connections to prevent leaks 10 Place silicone heat transfer compound on the tip of the temperature probes and install them in the temperature wells 11 Run separate electrical conduit between the control panel and the temperature probe electrical boxes DO NOT RUN THE TEMPER...

Page 4: ...om the junction box to the QUANTUM LX HD enclosure is to use the number 12 gauge blue and black wires which were used for common and 5VDC The most common electronic control panel problems are due to undersized AC power wiring poor grounds and control power supplied from lighting panels that have other devices tied to them that generate large amounts of AC line noise Please follow these directions ...

Page 5: ...e temperature probe from the well Place the temperature probe in a container of water along with a quality test thermometer 42 Wait for approximately two minutes and compare the thermometer reading with the temperature probe reading Enter in the correction for temperature if required 43 Step to the next temperature to be calibrated and locate the associated temperature probe on the compressor pack...

Page 6: ...UCTIONS 090 040 I MAR 2012 Page 6 TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB II TO QUANTUM HD CONTROL TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB AND OTHER MANUFACTURER S UNITS TO QUANTUM HD CONTROL QUANTUM LX HD PANEL QUANTUM LX HD PANEL ...

Page 7: ...y sizing control wires and other wiring specifications Throughout this document the term Electronic Control Panel is used to refer to the microprocessor mounted on the com pressor package or a Central Control System panel It is very important to read the installation instructions thoroughly before beginning the project Make sure you have drawings and instructions with your equipment If not call th...

Page 8: ...the three phase power wiring This must be sized in accordance to the NEC and any local codes relative to the highest rated circuit overload protection provided in the circuit The manufacturer may require a larger ground conductor than what is required by the NEC for proper steering of EMI from sensitive circuits This conductor must also be insulated to avoid inadvertent contact at multiple points ...

Page 9: ... in metal or other material by national or local codes conduits for the power feed 3 phase of constant speed starters may be PVC When not required to be in metal or other material by national or local codes conduits between a constant speed starter and the motor 3 phase may be PVC Any unshielded control voltage signal analog or communication wiring that does not maintain 12 inches of separation fr...

Page 10: ...using catastrophic failure Route the conduit to the sides or bottom of the panel and use a conduit drain If the conduit must be routed to the top of the panel use a sealable conduit fitting which is poured with a sealer after the wires have been pulled terminated and the control functions have been checked A conduit entering the top of the enclosure must have a NEMA 4 hub type fitting between the ...

Page 11: ...em providing shutdown protection for a Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter contactor still energized the compres sor auxiliary will continue to feed an okay signal to the Quantum LX panel This may allow the motor to be subjected to the fault condition on the 3 pha...

Page 12: ...ohnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 090 040 I 2012 03 Supersedes S90 130 I 2004 10 Subject to change without notice Published in USA 0812 GUI 50 2012 Johnson Controls Inc ALL RIGHTS RESERVED ...

Reviews: