background image

FRICK

®

 QUANTUM

LX/HD RETROFIT

INSTALLATION INSTRUCTIONS

090.040-I (MAR 2012)

Page 4

21. 

Refer to the panel wiring diagrams in the Maintenance 

manual  (090.020  M  or  090.040  M)  and  connect  the  red, 

black, and white wire of the twisted-three wire to the slide 

valve potentiometer. Cut off the shield wire at the slide valve 

indicator end and place tape or heat shrink tubing around 

the exposed shield so that it will not come in contact with 

the compressor or slide valve cover.

22. 

Connect the shield wire of the twisted-three wire to the 

control panel ground block in the control panel.

23. 

Connect the red, black, and white twisted-three wires 

to the microprocessor board, as shown on the panel wiring 

diagrams in manual 090.020-M or 090.040-M.

24.

 If the compressor is an RWB II model, locate the slide 

stop potentiometer. Verify that the existing wiring between 

the slide stop potentiometer and control panel is wired with 

Belden 8770 or equivalent.

25. 

Refer to the panel wiring diagrams in the manual 090.020-

M or 090.040-M and verify that the red, black, and white 

wires of the twisted-three wire to the slide stop potenti-

ometer are wired properly. Verify that the shield wire at the 

slide stop end is cut off and taped to prevent contact with 

the compressor. Leave slide stop cover off until the calibra-

tion procedure is complete.

26. 

Connect the red, black, and white twisted-three wires 

to the microprocessor board, as shown on the panel wiring 

diagrams in the manual 090.020-M or 090.040 M.

27. 

Connect the shield wire of the twisted-three wire to the 

control panel ground block in the control panel.

28. 

Before starting the AC control wiring, the following items 

should be checked in the compressor starter. Refer to the 

compressor motor starter diagrams.

A. 

The compressor requires a minimum of 2 KVA transformer 

for 120 VAC control and heater power.

B. 

The compressor starter must have a ground wire pulled 

from the three-phase source. The ground must be connected 

to the starter backplate and the neutral terminal (2) on the 

secondary side of the control transformer.

C. 

Verify  that  the  current  transformer  (CT)  is  placed  as 

shown on the motor starter diagram in the IOM and is sized 

according to the current transformer (CT) selection chart.

D. 

Verify that auxiliary contacts are provided on the compres-

sor and oil pump contactor (if oil pump is required).

E. 

Verify  that  the  compressor  motor  overloads  are  sized 

properly.

F. 

If the compressor and oil pump starters do not have inter-

posing relays already provided, the relays must be mounted 

and wired as shown on the drawings.

G. 

If converting from an RWB II to a 

QUANTUM

LX/HD

, con-

nect the motor amp signal from the current transformer in 

the motor starter (wires 3 and 4) directly to the analog board 

in the 

QUANTUM

LX/HD 

panel. On the RWB II, the number 

3 and 4 wires were connected to a current transducer in the 

junction box. The best way to get the CT  from the 

junction box to the 

QUANTUM

LX/HD

 enclosure is to use 

the number 12 gauge blue and black wires which were used 

for common and +5VDC.

The most common electronic control panel problems are 

due to undersized AC power wiring, poor grounds, and 

control  power  supplied  from  lighting  panels  that  have 

other devices tied to them that generate large amounts 

of AC line noise. Please follow these directions carefully. 

(For additional information on "Installation of Electronic 

Equipment in an Industrial Environment", see page 7)

Metal oxide varistors (MOV or surge suppressor) are rec-

ommended for the load/unload solenoid coils, compressor 

starter  coil,  oil  pump  starter  coil  (if  applicable)  and  liquid 

injection solenoid coil (if applicable). The MOVs should be 

placed directly at the coils of these devices. Placement of 

the  MOVs  at  the  control  panel  terminal  strip  negates  the 

surge suppression effect. For 100 VAC to 125 VAC operation, 

a General Electric part number V130LA10A is recommended. 

For 185 VAC to 254 VAC operation, a General Electric part 

number V275LA20A is recommended.

29. 

Using  12  AWG  or  larger  wire,  connect  the  control 

transformer in the compressor starter panel to the proper 

terminals in the 

QUANTUM

LX/HD 

control panel, as shown 

in the IOM on the compressor motor starter diagrams and 

the panel wiring diagrams. These wires are: black (1), white 

(2), and green (GND). (Copper ground only. Conduit ground 

is not acceptable.)

The main power wiring to the 

QUANTUM

LX/HD

 panel (line 

and neutral) must be 12 AWG or larger. A separate ground 

wire is also required for each 

QUANTUM

LX/HD

 panel and 

must also be at least a number 12 copper wire.

30. 

Connect the remaining control wires between the starter 

and the control panel, as shown in the IOM on the compres-

sor motor starter diagrams and the panel wiring diagrams. 

These control wires are typically:

A.

 Compressor start 

 

 

(18)

B. 

Compressor auxiliary 

 

 

(20)

C. 

Current transformer 

 

 

(3 and 4)

D.

 Oil pump start (if required) 

 

(8)

E.

 Oil pump auxiliary (if required) 

 

(19)

31.

 Connect the remaining package control wires, including 

options, to the control panel, as shown on the panel wiring 

diagrams in the manual 090.020-M or 090-040-O.

32. 

Before applying power to the 

QUANTUM

LX/HD

 control 

panel, make the following checks:

A. 

Check for loose connections or damage to the circuit 

boards or cables.

B. 

Check for wire clippings or metal drill filings on the 

circuit board or in the panel. Clean 

QUANTUM

LX/HD 

control  panel  thoroughly  before  applying  the  control 

power.

33. 

Make sure that the circuit breakers (1CB and 2CB) in the 

QUANTUM

LX/HD 

control panel are in the "OFF" position. 

Engage the electrical disconnect at the compressor starter.

34. 

Using a DIGITAL VOLTMETER, verify the AC line voltage 

in the 

QUANTUM

LX/HD

 control panel. The AC line voltage 

should  be  between  100  VAC  and  125  VAC  or  185  VAC  to 

254 VAC.

35. 

Check for AC volts (in millivolts) between AC neutral (2) 

and AC ground (GND). If the millivolt reading is greater than 

500  millivolts,  pull  the  electrical  disconnect  at  the  motor 

starter and reverify ground and neutral circuits.

36. 

Turn circuit breakers 1CB and 2CB to the "ON" position.

Summary of Contents for FRICK QUANTUM LX/HD

Page 1: ...UM LX HD CONTROL INSTALLATION INSTRUCTIONS Form 090 040 I MAR 2012 INSTALLATION File SERVICE MANUAL Section 90 Replaces S90 130 I OCT 2004 Dist 3 3a 3b 3c Please check www johnsoncontrols com frick for the latest version of this publication ...

Page 2: ...RIAL RECEIVED FOR SUITABILITY AND COMPLETENESS Instructions are provided for retrofit conversion from either RWB Electromechanical or RWB II Microprocessor Control to QUANTUM LX HD Control Other screw compressors not manufactured by Frick can also be converted to the QUANTUM LX HD Control Frick screw compressor pack ages where the compressor itself was not manufactured by Frick are considered to b...

Page 3: ... con nection available and will require cutting a hole and welding in a connection for the temperature well Seal all threaded connections to prevent leaks 10 Place silicone heat transfer compound on the tip of the temperature probes and install them in the temperature wells 11 Run separate electrical conduit between the control panel and the temperature probe electrical boxes DO NOT RUN THE TEMPER...

Page 4: ...om the junction box to the QUANTUM LX HD enclosure is to use the number 12 gauge blue and black wires which were used for common and 5VDC The most common electronic control panel problems are due to undersized AC power wiring poor grounds and control power supplied from lighting panels that have other devices tied to them that generate large amounts of AC line noise Please follow these directions ...

Page 5: ...e temperature probe from the well Place the temperature probe in a container of water along with a quality test thermometer 42 Wait for approximately two minutes and compare the thermometer reading with the temperature probe reading Enter in the correction for temperature if required 43 Step to the next temperature to be calibrated and locate the associated temperature probe on the compressor pack...

Page 6: ...UCTIONS 090 040 I MAR 2012 Page 6 TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB II TO QUANTUM HD CONTROL TRANSDUCER CONNECTION DIAGRAM FOR CONVERTING RWB AND OTHER MANUFACTURER S UNITS TO QUANTUM HD CONTROL QUANTUM LX HD PANEL QUANTUM LX HD PANEL ...

Page 7: ...y sizing control wires and other wiring specifications Throughout this document the term Electronic Control Panel is used to refer to the microprocessor mounted on the com pressor package or a Central Control System panel It is very important to read the installation instructions thoroughly before beginning the project Make sure you have drawings and instructions with your equipment If not call th...

Page 8: ...the three phase power wiring This must be sized in accordance to the NEC and any local codes relative to the highest rated circuit overload protection provided in the circuit The manufacturer may require a larger ground conductor than what is required by the NEC for proper steering of EMI from sensitive circuits This conductor must also be insulated to avoid inadvertent contact at multiple points ...

Page 9: ... in metal or other material by national or local codes conduits for the power feed 3 phase of constant speed starters may be PVC When not required to be in metal or other material by national or local codes conduits between a constant speed starter and the motor 3 phase may be PVC Any unshielded control voltage signal analog or communication wiring that does not maintain 12 inches of separation fr...

Page 10: ...using catastrophic failure Route the conduit to the sides or bottom of the panel and use a conduit drain If the conduit must be routed to the top of the panel use a sealable conduit fitting which is poured with a sealer after the wires have been pulled terminated and the control functions have been checked A conduit entering the top of the enclosure must have a NEMA 4 hub type fitting between the ...

Page 11: ...em providing shutdown protection for a Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter contactor still energized the compres sor auxiliary will continue to feed an okay signal to the Quantum LX panel This may allow the motor to be subjected to the fault condition on the 3 pha...

Page 12: ...ohnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 090 040 I 2012 03 Supersedes S90 130 I 2004 10 Subject to change without notice Published in USA 0812 GUI 50 2012 Johnson Controls Inc ALL RIGHTS RESERVED ...

Reviews: