background image

Mounting Procedure: Flush Thin Mount

The FMS-1655R flush thin mount model offers 

an attractive stainless steel faceplate with an 

ultra-thin enclosure (less than ¾” thick) that 

may be installed in any application where 

wall depth is either unknown or extremely 

limited. New construction applications can 

take advantage of the included wall box that 

may be installed during the rough-in phase. 

For retrofit applications not requiring electrical 

conduit termination, the unit may be installed 

using the retrofit mounting plate that simplifies 

the installation process. 

1. The FMS-1655R flush thin mount model 

should be mounted in a location that provides 

convenient access so the display may be 

viewed with minimal glare and the touch 

screen is easily accessible to facilitate 

silencing the unit in the event of an alarm 

condition. 

2. If this is a new construction project and the 

wall box has been installed, you may skip the 

next two steps. If this is a retrofit application 

and existing drywall is in place, then proceed 

with the next step to prepare the opening for 

the FMS-1655R flush thin mount model. 

3. Using the retrofit mounting plate (see 

Figure 2

) as a template, trace the inner outline 

onto the drywall at the desired mounting 

location with a pencil or marker. Also mark 

the location of the two mounting holes on 

the drywall. Cut along the traced outline 

with a drywall knife or saw, taking care not 

to make the opening too large. Drill out the 

two holes to clear access to the mounting 

clip nuts. Remove the cut section of drywall 

and discard. Be sure to brush off any drywall 

dust or remnants from the inside surface of 

the opening to ensure proper adhesion of the 

retrofit mounting plate. 

4. Remove the paper backing from the two 

adhesive strips on the retrofit mounting 

plate and insert it into the cut opening of the 

drywall. The retrofit plate should be oriented 

such that the corner notch is located at the 

lower left corner of the opening in the drywall, 

with the tabs bent towards you. Using the 

four tabs on the retrofit mounting plate as 

alignment guides, press the mounting plate 

onto the inside surface of the drywall opening 

firmly to ensure maximum adhesion.

5. The electrical connections must be 

terminated before installing the stainless 

steel faceplate of the FMS-1655R. Run the 

4-conductor, dual twisted pair, electrical 

connection from the nearest FMS-1655. Refer 

to the wiring diagram shown on 

page 7

 for 

details. 

6. Terminate the interface cable originating 

from the host controller at the 4-position and 

3-position terminal blocks on the back side 

of the FMS-1655R display, ensuring proper 

electrical connections. Power connections 

should be terminated at +V and GND 

of the 4-position terminal block, and the 

subnet connections should be terminated 

at NETWK+ and NETWK- at the 3-position 

terminal block (see page 7). Do not apply 

power until the faceplate has been securely 

fastened to the wall. 

7. With the electrical connections properly 

terminated, the stainless steel faceplate 

may be installed using the two flat head 

machine screws. For retrofit applications 

where the mounting plate has been affixed 

to the inside surface of the drywall, the two 

mounting screws thread into the clip nuts of 

the mounting plate. For those applications 

where the wall box has been installed, the two 

mounting screws fasten the faceplate directly. 

8. With power applied, the FMS-1655R should 

display the offline status of four stations at the 

default subnet addresses. 

 

Mounting Procedure: Surface Mount

The FMS-1655R surface mount model 

incorporates a low-profile display enclosure 

that may be mounted to any surface using 

wall anchors or the appropriate fastening 

hardware. For new construction applications, 

the FMS-1655R surface mount enclosure is 

designed to accommodate a standard single-

gang (2x4) wall box. 

This allows the wall box to be installed during 

the rough-in phase, and the appropriate 

electrical conduits to be installed as 

necessary. The FMS-1655R is configured at 

the factory for 

Standard View 

mode, which 

most closely matches that of the companion 

FMS-1655 display. The user may change 

the factory-default settings by following the 

procedures outlined in the 

Quick Start Guide

 

(page 3) section of this manual. 

SUBHEAD

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

-

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

INSTALLATION MANUAL

Fig 2. Retrofit Mounting Plate

Summary of Contents for FMS-1655 Series

Page 1: ...beginning installation North American Emissions Compliance United States Canada Installation This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Risk of Property Damage Ensure that the power source conforms to the req...

Page 2: ...ings 6 Wiring the FMS 1655R to Nearest JCI Controller 7 Notes 8 PROGRAMMING MANUAL Introduction 9 Main Setup Menu 9 Unit Setup 10 Configuring Monitor Settings 10 Configuring Audible Alert Settings 10 System Setup 11 Managing System Security Passwords 12 Adding New Passwords 12 Deleting an Existing Password 12 Purging All Passwords 12 Display Setup 12 Configuring the Safety HaloTM 12 Selecting Disp...

Page 3: ...ry RS 485 interface Power may be supplied by FMS 165x or by separate power supply 18 to 32 Vdc Touchscreen User Interface LCDSizeandType 3 2 diagonal transmissive Resolution 240 pixels x 320 pixels portrait mode Viewing Area 50 60 mm x 66 80 mm Color Depth 18 bit or 262K colors Backlight Color White Luminous Intensity min 2500 cd m2 Mechanical Mounting Options Surface Plastic Flush Brushed Stainle...

Page 4: ...es the setup and configuration of the remote display The display incorporates bright background color changes to indicate up to five different statuses at the companion FMS 1655 Green represents normal status whereby the monitored parameter is within defined normal operating limits Yellow indicates that the monitored parameter has drifted outside of the normal operating limits and is approaching t...

Page 5: ...rmly to ensure maximum adhesion 5 The electrical connections must be terminated before installing the stainless steel faceplate of the FMS 1655R Run the 4 conductor dual twisted pair electrical connection from the nearest FMS 1655 Refer to the wiring diagram shown on page 7 for details 6 Terminate the interface cable originating from the host controller at the 4 position and 3 position terminal bl...

Page 6: ...surface mount Safety HaloTM backplate has been properly installed the electrical connections should be terminated before installing the cover with the display Run the 4 conductor dual twisted pair electrical connection from the nearest controller Refer to the wiring diagram shown on page 7 for details 6 Terminate the interface cable originating from the host controller at the 4 position and 3 posi...

Page 7: ...exclamation point action icon Figure 8 indicates that the monitored parameter has reached a critical condition and is outside of the allowable limits of the target setpoint This visual indication is supplemented by an audible alarm to indicate that attention is required The FMS 1655R incorporates a full color touchscreen display and with an intuitive menu system that allows the user to quickly set...

Page 8: ...yed parameter in the upper LCD window gray box on the main display Tapping this field invokes a details screen which includes all six of the analog input parameters currently being monitored at the companion FMS 1655 To change which parameter is displayed on the main screen of the FMS 1655R select the individual parameter on the details screen and tap the OK button Adding Password Security The FMS...

Page 9: ... mode is selected may be adjusted either by using the hotspots on the main display or by selecting Display Setup Set Time Date The FMS 1655R is also designed to request time and date settings periodically from the companion FMS 1655 assuming it resides on a network that has a time server available This ensures that the time and date are accurate on the FMS 1655R main display INSTALLATION MANUAL 6 ...

Page 10: ...Due to continuous improvement JCI reserves the right to change product specifications without notice INSTALLATION MANUAL Wiring FMS 1655R to Nearest JCI Controller 7 CN7 CN3 NETWK NETWK GND V ...

Page 11: ...s improvement TRIATEK reserves the right to change product specifications without notice Due to continuous improvement JCI reserves the right to change product specifications without notice INSTALLATION MANUAL Notes 8 ...

Page 12: ...ivity while configuration screens automatically time out after 60 seconds This prevents unauthorized access to the user menu system should a unit be inadvertently left unattended at one of the configuration screens Main Setup Menu All of the configuration screens that allow the settings of the FMS 1655R to be configured for a specific application originate from the top level of the user interface ...

Page 13: ... status of the companion FMS 1655 Tapping Finish at the Monitor Setup configuration screen stores that subnetwork address of the companion FMS 1655 and begins the polling process immediately Configuring Audible Alert Settings The Audible Alert option on the Unit Setup menu provides support for configuring the settings associated with the audible alarming capabilities of the FMS 1655R and invokes t...

Page 14: ...m limits and is in need of attention This critical condition is indicated by a red background and a red exclamation point action icon The Safety Halo status indicator if enabled will flash quickly in red to indicate the Alarm status A blue background indicates that Neutral isolation mode is selected at the companion FMS 1655 This mode is indicated by an action icon represented as a red circle with...

Page 15: ... Safety Halo option on the Display Setup menus allows you to configure the settings for the Safety Halo bezel including the Nightly Auto Dim feature This feature allows the Safety Halo to automatically reduce its brightness to the specified percentage at the specified Starting Hour and return to normal brightness at the specified Ending Hour To configure the Safety Halo select the Safety Halo opti...

Page 16: ...FMS 1655R is designed to synchronize its local time and date with the network resident controller it is monitoring thereby allowing the time based features to operate accurately These include the Alarm Buzzer Quiet Period and the Safety HaloTM Auto Dim Period Selecting this option invokes the time configuration screen as shown in Figure 25 The colon between the hours and minutes automatically appe...

Page 17: ...your unit Resetting the FMS 1655R The Reset Monitor option on the Diagnostics menu allows the user to perform a soft reboot of the remote display and completely re initialize the unit This option may be useful during the installation process when changes have been made to the network parameters subnetwork address Selecting this option invokes the warning message as shown in Figure 28 informing the...

Page 18: ...Due to continuous improvement JCI reserves the right to change product specifications without notice User Menu Flow Diagram 15 PROGRAMMING MANUAL ...

Page 19: ...Central Monitoring Station JCI FMS 1655 The Next Generation in Critical Airflow Controls FMS 1655 Room Pressure Remote Display Installation and Programming Manual LB FMS1655 RS LB FMS1655 RT Code No LIT 12013124 Rev A Issued August 2018 1 414 524 1200 Johnson Controls 5757 N Green Bay Ave P O Box 591 Milwaukee WI 53201 ...

Reviews: