Network Room Module Technical Bulletin
30
Troubleshooting
Table 10: Troubleshooting NRM Installation
Problem Cause/Action
No indication is on LCD.
No power available. Check the wiring and supply voltage to the
module.
Maintenance icon
is visible on
display.
One or more of the following has occurred:
•
PT1000 temperature sensor in the NRM has failed.
Replace the NRM module.
•
No communication with the FX controller. Check the bus
wiring to the display (local link) bus of the controller and
that the +, - and COM wires are correctly connected.
•
An off normal condition is being reported by the controller.
A symbol does not appear as expected.
Verify that the configuration properties to enable the display of
the symbol are set correctly in the Room Sensor object in the
FX controller.
Verify that the FX controller to which the NRM module is
connected has been loaded with the correct configuration.
A manual change at the NRM does not
work as expected (setpoint change, fan
speed override or occupancy
command).
Verify that the configuration properties to enable the command
are set correctly.
Using the FX CommPro Commissioning Tool, check that the
values of the network variable outputs from the Room Sensor
object respond in accordance with the display changes as the
dial is rotated or the fan push button is pressed.
Verify that the controller to which the NRM module is connected
has been loaded with the correct configuration.
NRM shows a fan override status but it
is not active in the connected controller.
Verify that the controller to which the NRM module is connected
has been loaded with the correct configuration and that the
configuration is designed to react correctly to an override
status. Check for other conditions that could override the NRM
module override.
Display shows a different value for the
setpoints as the FX controller.
Verify that the controller to which the NRM module is connected
has been loaded with the correct configuration.
Verify that the configuration properties have been set correctly.
Using the FX CommPro Commissioning Tool, check that the
value of the relevant network variable output of the Room
Sensor object is equal to the value on the LCD. If not, replace
the NRM module.