FEATURES
1-4
TC-18004-rev.2
The air conditioning capacity is saved automatically depending on a situation and detecting amount of
human activity by adopting the motion sensor kit. In addition, the operation can be stopped automatically
if the absent situation continues for more than 30 minutes
*1)
. The motion sensor allows maintaining the
comfortable indoor environment and eliminating the unnecessary operation
*2)
.
*1)
: The default setting is “30 minutes”. However, the setting is changeable.
*2)
: The default setting is “Running Operation”. However, “Automatic Stop” can be selected by setting
from the remote control switch.
• Detecting Area for Human Activity
Detecting Diameter: Approx. 23 ft. x 23.6 ft. (7.0m x 7.2m)
(0.8m…height from floor surface)
The motion sensor may not detect the human
activity at the space just under the indoor unit
(5.9ft. x 23 ft. (1.8m x 7.0m).)
Motion Sensor Control
Detecting Area
5.9 ft.
(1.8m)
29.5 ft.
(9m)
23.6 ft.
(7.2m)
Floor-to-
Ceiling
Height
8.9 ft. (2.7m)
Example for 15 to 36MBH indoor units
23.0 ft. (7m)
2.6 ft. (0.8m) from Floor Level
Detecting Area
Detecting Area
NOTES: About Motion Sensor (Optional, Model: SOR-NEP)
1. The motion sensor detects the human activity. However, if someone is in a room with a bit motion, the
motion sensor may detect as absence.
2. The motion sensor may detect as human activity, if the indoor unit with the motion sensor is installed
near a moving object which is different temperature against atmosphere.
3. The motion sensor may detect as absence in the case that the indoor unit with the motion sensor is
installed to a high ceiling even if someone is in a room.
Summary of Contents for CICS015B21S
Page 2: ......
Page 17: ...CEILING SUSPENDED TC 18004 rev 2 2 3 2 4 Dimensional Data Model H Y C ICS015B21S Unit inch mm ...
Page 18: ...CEILING SUSPENDED 2 4 TC 18004 rev 2 Unit inch mm Model H Y C ICS024B21S ...
Page 34: ......
Page 60: ......
Page 66: ...Annex 4 2 Way Cassette Type Indoor Unit Models H Y C IC2018B21S and H Y C IC2024B21S ...
Page 72: ... 2018 Johnson Controls Inc TC 18004 rev 2 Code No LIT 12013004 Revised September 2019 ...