OPTIONAL PARTS
3-12
TC-18004-rev.2
3. Installation
● For this condensate pump, the condensate piping connection changes from VP20 to VP25. (PVC pipe).
● The condensate piping and the refrigerant piping can be connected from only the top right side of the
indoor unit viewing from the front.
(1) Maintain the service space at the right side of the indoor unit viewing from the front as shown in the
figure below when the condensate pump is installed.
(2) Select the installation place where a sufficient ceiling
height is maintained to facilitate the condensate piping
and 1/25 ~ 1/100 ratio of down-slope can be created.
(3) The following figures show the installation dimensions.
(The condensate pump is installed at the shaded part.)
Unit: inch (mm)
Model
DUPC-63K1
DUPC-160K1
Applicable Indoor Unit Model
(H,Y,C)ICS015B21S
(H,Y,C)ICS024-036B21S
Field Refrigerant Pipe
Gas
1/2 (12.7)
5/8 (15.88)
Flare Nut Connection
Liquid
1/4 (6.35)
3/8 (9.52)
Indoor Unit
(Front Side)
Min. 11-13/16 inches
(300mm)
Condensate Pump
27-3/16 (690)
3-3/8 (85)
5-
11
/16 (145)
4-5/16
(110)
23-5/8 (600)
3-3/8 (85)
27-3/16 (690)
5-1/16 (128)
3-3/8 (85)
2-15/16
(75)
1-13/16
(46)
5-11/16
(145)
5-13/16
(148)
6-5/16
(160)
5-
11
/16 (145)
9-1/14 (235)
3-15/16 (100)
3-
15/16 (100)
DUPC-63K1
DUPC-160K1
Indoor Unit
(Front Side)
(Rear Side)
(Front Side)
(Rear Side)
Indoor Unit
Electrical Box
Electrical Box
024
Ty
pe: 50 (1270)
030 and 036
Ty
pe: 62-3/16 (1580)
37-13/16 (960)
Refrigerant Liquid Piping
(
φ
Flare Nut
)
B
Refrigerant Gas Piping
(
φ
Flare Nut
)
A
Air Inlet
Air Outlet
Condensate Pump
(Max. Drain-up Height
)
Condensate Piping Connection
(PVC, VP25)
(Accessory)
L-shaped Condensate Pipe
Condensate Hose
Condensate Hose
Refrigerant Gas Pipe
(Accessory)
Ceiling
Ceiling
Refrigerant Liquid Pipe
(Accessory)
View from Top
View from Left
View from Top
View from Left
Wiring Connection
(for Indoor Unit)
Cap
(Attached to Indoor Unit)
Wiring Connection
(for Indoor Unit)
Cap
(Attached to Indoor Unit)
Air Outlet
Air Inlet
Condensate Pump
Refrigerant Liquid Pipe
(Accessory)
Refrigerant Gas Pipe
(Accessory)
(Accessory)
L-shaped Condensate Pipe
(Max. Drain-up Height
)
Condensate Piping Connection
(PVC, VP25)
Refrigerant Liquid Piping
(
φ
Flare Nut
)
B
Refrigerant Gas Piping
(
φ
Flare Nut
)
A
Unit: inch (mm)
㸯
4-5/8 (118)
㸯
3-3/8 (85)
1-13/16
(46)
5-11/16
(145)
5-13/16
(148)
6-5/16
(160)
4-5/16
(110)
23-5/8 (600)
㸯
3-
15/16 (100)
2-15/16
(75)
3-15/16 (100)
9-1/14 (235)
㸯
3.1 Installation Space and Position
Summary of Contents for CICS015B21S
Page 2: ......
Page 17: ...CEILING SUSPENDED TC 18004 rev 2 2 3 2 4 Dimensional Data Model H Y C ICS015B21S Unit inch mm ...
Page 18: ...CEILING SUSPENDED 2 4 TC 18004 rev 2 Unit inch mm Model H Y C ICS024B21S ...
Page 34: ......
Page 60: ......
Page 66: ...Annex 4 2 Way Cassette Type Indoor Unit Models H Y C IC2018B21S and H Y C IC2024B21S ...
Page 72: ... 2018 Johnson Controls Inc TC 18004 rev 2 Code No LIT 12013004 Revised September 2019 ...