background image

OPTIONAL PARTS

TC-18004-rev.2

 3-21

3.7  Infrared (IR) Receiver Kit: CSIRK01

Dimensional Data

Unit: inch (mm)

Installation State

4-1/2 (115)

4 (102)

15/16 (23.3)

IR Receiver Kit

Summary of Contents for CICS015B21S

Page 1: ...NVERTER DRIVEN MULTI SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS Engineering Manual TC 18004 Technical Catalog for Outdoor Unit Indoor Units Ceiling Suspended H Y C ICS015B21S H Y C ICS024B21S H Y C ICS030B21S H Y C ICS036B21S ...

Page 2: ......

Page 3: ...d against possible damage or injury that might occur in an earthquake if the unit is not installed correctly injuries may occur due to a falling unit Use appropriate Personal Protective Equipment PPE such as gloves and protective goggles and where appropriate have a gas mask nearby Also use electrical protection equipment and tools suited for electrical operation purposes Keep a wet cloth and a fi...

Page 4: ...n any location where animals and plants can come into direct contact with the outlet air stream Exposure could adversely affect the animals and plants Do not install the unit with any downward slope to the side of the drain adapter If you do you may have condensate flowing back which may cause leaks Be sure the condensate hose discharges water properly If connected incorrectly it may cause leaks D...

Page 5: ...gases can be generated from decomposition Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present If you do toxic gases can seep into breathable air spaces and can cause respiratory issues If the condensate pipe is installed incorrectly water leakage and damage to the ceiling floor furniture or other possessions may result If condensate...

Page 6: ...the cycle the sizes of the charging connections have been changed from R407C type and R22 type It is necessary to verify the appropriate tools are on hand before performing installation work Use refrigerant pipes and joints which are approved for use with R410A A compressor unit comprises a pressurized system Never loosen threaded joints while the system is under pressure and never open pressurize...

Page 7: ...on cable must be a minimum of AWG18 0 82mm2 2 Conductor Stranded Copper Shielded cable must be used for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors When shielded cabling is applied proper bonding and termination of the cable shield is required as per Johnson Controls guidelines Plenum and...

Page 8: ... 18 2 11 4 Wiring Diagram 2 19 3 Optional Parts 3 1 3 1 Line Up 3 1 3 2 Air Filter F 56MP K1 F 90MP K1 and F 160MP K1 3 2 3 3 Filter Box B 56MP B 90MP and B 160MP 3 5 3 4 Motion Sensor Kit SOR NEP 3 8 3 5 Condensate Pump Kit DUPC 63K1 and DUPC 160K1 3 11 3 6 Duct Adapter PD 100 3 20 3 7 Infrared IR Receiver Kit CSIRK01 3 21 3 8 3P Connector Cable PCC 1A 3 24 3 9 Remote Sensor THM R2A 3 24 3 10 Rel...

Page 9: ...en combination of the scroll compressor and inverter provides the best air conditioning for small and medium office buildings VRF System Johnson Controls has developed the VRF system with its customers in mind This system allows the interconnection of indoor units for all our VRF air conditioners This system provides the consumer with greater flexibility for installation which means that the air c...

Page 10: ... New Fan Runner New L Shaped Fin Fan Casing Air Outlet Diffuser Adopting Amenity Auto Louver Large sized amenity auto louver with the same color as indoor unit body is adopted It softens the discomfort by temperature irregularity and cold draft The auto louver as a shutter during the operation stoppage improves design Temperature Distribution Ceiling Floor 3 3 feet 1m 3 3 feet 1m Temp o F o C 93 2...

Page 11: ...sensor can be set and controlled only from the wired controller NOTE If the high speed 2 setting 02 is selected from the remote control switch the airflow volume of HIGH 2 and HIGH will be equaled as shown in the table Because the airflow volume HIGH 2 and HIGH are used as HH2 in high speed 2 setting High Speed Mode C5 Airflow Volume Mode HIGH 2 HIGH MED LOW Standard 00 HH2 Hi Me Lo High Speed 1 1...

Page 12: ... 7 2m 0 8m height from floor surface The motion sensor may not detect the human activity at the space just under the indoor unit 5 9ft x 23 ft 1 8m x 7 0m Motion Sensor Control Detecting Area 5 9 ft 1 8m 29 5 ft 9m 23 6 ft 7 2m Floor to Ceiling Height 8 9 ft 2 7m Example for 15 to 36MBH indoor units 23 0 ft 7m 2 6 ft 0 8m from Floor Level Detecting Area Detecting Area NOTES About Motion Sensor Opt...

Page 13: ...sure the frequency of detecting human activity in the period of time Determine amount of the human activity depending on the calculated reaction rate frequency Reaction Rate Frequency Detected Counts of Human Activity Measured Counts of Time Change to each operating mode depending on amount of the human activity and the elapsed time Control automatically by each operating mode Measure the frequenc...

Page 14: ... sensors switch to MODE 3 After the operation is stopped the operation will not restart even if detecting the human activity due to stopped by the wired controller The indoor unit without the motion sensor and the indoor unit with the motion sensor can be mixed In this case the indoor unit without the motion sensor will also stop as shown in the figure below 2 Transmission Wire for H LINK ll Trans...

Page 15: ...Unit Type CS Ceiling Suspended Type CS Capacity MBH 015 Refrigerant Type B R410A B Power Supply 2 208 230Volts 1Phase 60Hz 2 1 1st Generation 1 S Standard Type S 2 2 Line up Type Capacity Model RT MBH Indoor Unit Ceiling Suspended 1 3 15 H Y C ICS015B21S 2 0 24 H Y C ICS024B21S 2 5 30 H Y C ICS030B21S 3 0 36 H Y C ICS036B21S 2 1 Unit Nomenclature Model Descriptions Example ...

Page 16: ...38 35 31 28 0 0 0 27 000 7 9 43 40 36 31 0 0 0 36 000 10 5 40 000 11 7 H Y C ICS015B21S Ceiling Suspended Type AC 1Phase 208 230V 60Hz R410A 24 21 18 14 5 847 741 635 512 24 000 7 0 530 459 388 318 15 13 11 9 H Y C ICS024B21S 48 45 41 35 1236 1094 900 706 35 31 25 5 20 160 Flare Nut Connection with Flare Nuts VP25 VP25 VP25 50 0 160 VP25 30 000 8 8 34 000 10 0 44 42 37 32 1059 935 777 600 30 26 5 ...

Page 17: ...CEILING SUSPENDED TC 18004 rev 2 2 3 2 4 Dimensional Data Model H Y C ICS015B21S Unit inch mm ...

Page 18: ...CEILING SUSPENDED 2 4 TC 18004 rev 2 Unit inch mm Model H Y C ICS024B21S ...

Page 19: ...CEILING SUSPENDED TC 18004 rev 2 2 5 Models H Y C ICS030B21S and H Y C ICS036B21S Unit inch mm ...

Page 20: ...rainer 6 Electronic Expansion Valve 7 Electrical Control Box 8 Refrigerant Gas Pipe Connection with f1 2 12 7 Flare Nut 9 Refrigerant Liquid Pipe Connection with f1 4 6 35 Flare Nut 10 Condensate Pipe VP20 OD f1 26 11 Motor for Auto Swing 12 Condensate Pan 13 Air Inlet Grille 14 Air Filter 15 Air Outlet 16 Air Inlet Model H Y C ICS015B21S ...

Page 21: ...xpansion Valve 7 Electrical Control Box 8 Refrigerant Gas Pipe Connection with f5 8 15 88 Flare Nut 9 Refrigerant Liquid Pipe Connection with f3 8 9 52 Flare Nut 10 Condensate Pipe VP20 OD f1 26 11 Motor for Auto Swing 12 Condensate Pan 13 Air Inlet Grille 14 Air Filter 15 Air Outlet 16 Air Inlet Model H Y C ICS024B21S Unit inch mm ...

Page 22: ...lve 7 Electrical Control Box 8 Refrigerant Gas Pipe Connection with f5 8 15 88 Flare Nut 9 Refrigerant Liquid Pipe Connection with f3 8 9 52 Flare Nut 10 Condensate Pipe VP20 OD f1 26 11 Motor for Auto Swing 12 Condensate Pan 13 Air Inlet Grille 14 Air Filter 15 Air Outlet 16 Air Inlet Models H Y C ICS030B21S and H Y C ICS036B21S Unit inch mm ...

Page 23: ... Output W Quantity Insulation Class Model 20 20 Heat Exchanger Type 3 3 3 3 Multi Pass Cross Finned Tube Copper Tube H Y C ICS015B21S H Y C ICS024B21S H Y C ICS030B21S H Y C ICS036B21S 20 20 Maximum Operating Pressure Total Face Area 35 8 50 6 74 2 Number of Coil Unit 1 1 1 1 Indoor Fan 1 1 1 1 Indoor Fan Motor 50 80 160 160 DC Motor E E E E 1 1 1 1 Aluminum Sirrocco Fan 155 6 1 8 6 1 8 6 1 8 6 1 ...

Page 24: ...ditions Indoor Air Inlet Temperature 80o F DB 26 7o C DB 67o F WB 19 4o C WB Outdoor Air Inlet Temperature 95o F DB 35 0o C DB Piping Length 24 ft 7 3 16 in 7 5m Piping Lift 0 ft 0m NOTE If there is a cornice on the ceiling measure the dimension from the front or undersurface For Single Installation For Parallel Installation Min 1 9 16 40 Min 11 13 16 300 Unit inch mm Min 11 13 16 300 Min 1 9 16 4...

Page 25: ...S 0 9 15 0 080 0 72 H Y C ICS030B21S 1 2 15 0 160 0 94 H Y C ICS036B21S 2 0 15 0 160 1 60 VOL Rated Unit Power Supply Voltage V PH Phase HZ Frequency Hz MCA Minimum Circuit Ampacity A MFA Maximum Fuse Ampacity A OPT Rated Motor Output kW FLA Full Load Ampacity A NOTE Power supply voltage should be satisfied with the following Supply Voltage Rated Voltage within 10 Starting Voltage Rated Voltage wi...

Page 26: ... 10 Sound Data NOTE Operation sound is equivalent to an anechoic chamber free space Noise level will be increased by the surrounding noise and echoes Model H Y C ICS015B21S Model H Y C ICS030B21S Model H Y C ICS036B21S Model H Y C ICS024B21S ...

Page 27: ...lve Unit inch mm Model Distributor A Gas Pipe Connection B Liquid Pipe Connection C OD T D OD T H Y C ICS015B21S 7 Pass f1 2 12 70 f1 4 6 35 f1 2 t0 031 12 7 0 8 f1 2 t0 031 12 7 0 8 H Y C ICS024B21S 9 Pass f5 8 15 88 f3 8 9 52 f5 8 t0 039 15 88 1 0 f1 2 t0 031 12 7 0 8 H Y C ICS030B21S 9 Pass f5 8 15 88 f3 8 9 52 f5 8 t0 039 15 88 1 0 f1 2 t0 031 12 7 0 8 H Y C ICS036B21S 9 Pass f5 8 15 88 f3 8 9...

Page 28: ...for details Automatic Cooling and Heating Operation It is applicable only for the Heat Recovery System Defrosting Operation The sequence may be different depending on the outdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for details 2 11 2 Standard Operation Sequence I U Indoor Unit Auto Cooling Heating Operation I U Air Intake Temp I U Air Intake Temp Set Temp Set Te...

Page 29: ...Dry Operation Is compressor running for more than 15 min 1 1 The check interval differs depending on the conditions I U Electronic Expansion Valve Completely Closed No No Yes MIF Operation at Set Fan Speed In case of Dry Operation MIF Operation OFF for 6 min Either Gas or Liquid Pipe Surface Temp of Indoor Heat Exchanger Yes Elapsed Time 15 min Pipe Surface Temp 2 36o F 2o C I U Indoor Unit a a 2 ...

Page 30: ...tdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for details 149o F 65o C 149o F 65o C Thermo ON OFF Control for Indoor Unit I U Indoor Unit Heating Operation I U Air Outlet Temp Thermo OFF Yes No 149o F 65o C 149o F 65o C No Yes I U Air Outlet Temp Elapsed Time 3 min Thermo ON Set Temp is lower than Air Intake Temp Prevention Control for Excessively High Outlet Air Te...

Page 31: ... the same wired zone controller are moved to Mode 3 then the operation is stopped from the wired zone controller Operation Stop Operation Start Much human activity is accumulated for five times within a 10 minute period or the setting is changed for the motion sensor on the wired zone controller Much human activity is accumulated for three minutes within a 10 minute period or the setting is change...

Page 32: ...tor Automatic Reset Non Adjustable each one for each motor Thermostat Cut Out o F o C Cut In o F o C Chip Ceramic PTC Thermistor o F 212 o C 100 For Control Circuit Fuse Capacity A 5 Freeze Protection Thermostat Cut Out o F 32 o C 0 Cut In o F 51 8 o C 11 Thermostat Differential o F 35 6 o C 2 2 11 3 Safety and Control Device Setting ...

Page 33: ...CEILING SUSPENDED TC 18004 rev 2 2 19 2 11 4 Wiring Diagram Models H Y C ICS015B21S H Y C ICS024B21S H Y C ICS030B21S and H Y C ICS036B21S ...

Page 34: ......

Page 35: ...ter PD 100 3 7 Infrared IR Receiver Kit CSIRK01 3 8 3P Connector Cable PCC 1A 3 9 Remote Sensor THM R2A 3 10 Relay and 3 Pin Connector Kit PSC 5RA 3 11 Wired Controller CIW01 3 12 Simplified Wired Controller CIS01 3 13 Wireless Controller CIR01 3 14 Mini Central Controller CCM01 3 15 Large Central Controller CCL01 3 16 Computerized Central Controller Software Adapter CCCS01 CCCA01 Refer to the Eng...

Page 36: ... 22 7 16 570 28 9 16 726 20 10 30 40 0 Pa 2 9 20 5 9 40 C F 160MP K1 A F 56MP K1 B F 90MP K1 B A C Mark Model inch mm Tether Filter Pressure Drop Characteristics Initial Pressure Drop m 3 min cfm 353 706 1059 1412 psi Frame Model Name Filter Stopper Filter Stopper Air Filter Optional Dimensional Data Indoor Unit with Air Filter Air Filter with Indoor Unit Air Inlet Grille Filter Box Optional ...

Page 37: ...NOTES 1 The patience time during operation is for reference it will change depends on the installation environment In case of operating in the oily atmosphere the patience time is extremely shorter than the reference time 2 Make sure to exchange the air filter optional after it passed the patience time Do not reuse it by washing 3 Each air filter optional is shipped by one set two filters per one ...

Page 38: ...e as in the figure above and is unnecessary to adjust Loosen the screw if it is necessary but do not remove 3 Secure the air filter optional by pushing the filter to the filter box frame and rotating the filter holder on the central rail 90 after attaching to the indoor unit Insert the air filter optional into the filter box while paying attention to the AIR FLOW direction on the air filter option...

Page 39: ...rting string from the indoor unit Refer to figures A and B below 3 While the air inlet grille is being opened depress the knobs of the hinge push the air inlet grille toward the arrow direction and remove the air inlet grille According to procedures 1 to 3 below B A 1 2 3 Side Plate Round Hole Supporting String Supporting String Square Hole Side Plate Air Inlet Grille Indoor Unit Indoor Unit Air I...

Page 40: ...g the hooks push up the other side of the filter box and fit the holes on the rear side of the filter box and the screw holes on the rear side of the indoor unit 4 Tighten the securing screws M4 three on the rear side then tighten the screws M4 three or four on the air outlet side 5 Loosen the securing screw of the top plate for the filter box Push up to the highest position then fasten the securi...

Page 41: ...r box frame and rotating the filter holder on the central rail 90 after attaching to the indoor unit Insert the air filter optional into the filter box while paying attention to the AIR FLOW direction on the air filter optional so as not to be upside down NOTES The fixed position of the support is made before shipping and is unnecessary to adjust Reposition the filter holder to the factory setting...

Page 42: ...OPTIONAL PARTS 3 8 TC 18004 rev 2 3 4 Motion Sensor Kit SOR NEP Dimensional Data Unit inch mm Installation State 4 1 2 115 4 102 Motion Sensor Kit SOR NEP ...

Page 43: ...y installed 2 Be sure to turn OFF the power supply of the indoor unit 3 Remove the right side cover 4 Remove the controller cover attached to the lower cover 1 Insert screwdriver or a stick maximum f3 16 inch 5mm into the service hole at the lower right side of lower cover 2 Press the service hole to remove the controller cover 1 Open the air inlet grille 2 Remove the fixing screw M4 3 Push the si...

Page 44: ...tween insulations 3 Catch two hooks of the motion sensor kit onto the square holes Pay attention to the direction of the motion sensor kit when it is attached NOTE Check whether the motion sensor kit is securely fixed NOTE After running the connecting cable clamp the extra length of the connecting cable using the cable band and store it inside the electrical box After the installation work is comp...

Page 45: ...on 25 3 8 645 Packed with 3 1 1 for Wrapping Condensate Piping 8 Insulation 3 8T x 5 1 8 x 9 1 16 10T x 130 x 230 2 2 for Wrapping Condensate Piping Connection 9 Insulation 3 8T x 1 15 16 x 7 7 8 10T x 50 x 200 1 1 for Wrapping Condensate Piping Connection 10 Insulation 3 16T x 2 13 16 x 2 13 16 5T x 72 x 72 1 1 for Vertical Condensate Pipe 11 Insulation 1 16 x 7 7 8 x 6 5 16 2T x 200 x 160 1 1 fo...

Page 46: ... 128 3 3 8 85 2 15 16 75 1 13 16 46 5 11 16 145 5 13 16 148 6 5 16 160 5 11 16 145 9 1 14 235 3 15 16 100 3 15 16 100 DUPC 63K1 DUPC 160K1 Indoor Unit Front Side Rear Side Front Side Rear Side Indoor Unit Electrical Box Electrical Box 024 Type 50 1270 030 and 036 Type 62 3 16 1580 37 13 16 960 Refrigerant Liquid Piping φ Flare Nut B Refrigerant Gas Piping φ Flare Nut A Air Inlet Air Outlet Condens...

Page 47: ...e hole for the piping connection in the ceiling as shown in the figure at the right 3 Open the air inlet grille and remove the side cover Refer to the Installation and Maintenance Manual for removing 4 Connect the refrigerant pipes 1 and 2 to the indoor unit Use two wrenches 5 Wrap the insulation attached to the indoor unit around the flare connection If installing this condensate pump kit after m...

Page 48: ...e field supplied completely around the PVC pipe connection Securely connect the pipes at the following A and B in order to prevent water leakage Securely fix the pipe connection at C using the cable band Do NOT use adhesive Create 1 25 1 100 of a down slope ratio for the PVC piping Flare Nut Field Refrigerant Pipe The insulation is required Indoor Unit Pipe Insulation Attached to Indoor Unit Ceili...

Page 49: ... indoor unit to the connection at the drain up mechanism 1 with the condensate hose attached to the indoor unit Fix each condensate pipe connection using the hose band attached to the indoor unit NOTE Do not use adhesive at the condensate hose connection because the condensate hose connection is required to be removed for servicing 8 Wrap two insulations attached to the indoor unit around the hose...

Page 50: ...t to apply an external force to the terminal connections of the wirings If fixing is not completed it may cause heat generation or a fire Do not open the service cover for the indoor or outdoor unit without turning OFF the main power supply Otherwise an electrical shock may occur DC12V 1 2 CN36 1 2 CN14 MD FSD DC13V CN36 White CN14 Blue Electrical Box PCB1 Disconnect the connector for CN14 Blue an...

Page 51: ...densate pan If the end of the condensate pipe cannot be checked visually remove the right side cover and check the drainage from the transparent service access door at the condensate pump If the water overflows from the condensate pan the condensate piping is not providing adequate drainage Recheck the condensate piping c Pour 51 oz to 68 oz 1500cc to 2000cc of water gradually from the air outlet ...

Page 52: ...tely five minutes The sound of water flowing may be heard because the drain up mechanism drains the drain water It is not an abnormality Drain the water from the drain plug if the indoor unit is not used for a long time Removing Water Tank 1 Remove the screw for the fixing plate 2 Remove the water tank according to procedures 1 through 4 in the figure below 3 Clean inside the water tank with a bru...

Page 53: ...f the condensate pump or float switch or an abnormality of condensate piping may occur Stop the indoor unit operation and contact your distributor 1 The alarm code 01 is indicated on LCD of remote control switch 2 Water leakage occurs at the indoor unit 9 Troubleshooting ...

Page 54: ...it amount Doing so could cause condensation 2 Do not install the unit where abnormal odors are in the atmosphere 3 The duct adapter provides a maximum quantity of fresh air intake of approximately 18cfm 0 5m3 min for 3 3 ft 1m straight pipe duct When more fresh air intake is required be sure to install the dedicated outside air system In this case do not utilize the dedicated outside air system 4 ...

Page 55: ...OPTIONAL PARTS TC 18004 rev 2 3 21 3 7 Infrared IR Receiver Kit CSIRK01 Dimensional Data Unit inch mm Installation State 4 1 2 115 4 102 15 16 23 3 IR Receiver Kit ...

Page 56: ...r supply completely before setting the DIP switches installation work and electrical wiring work for IR receiver kit If not it may cause an electric shock 4 Remove the controller cover attaching to the lower cover 1 Insert screwdriver or a stick maximum f3 16 inch 5mm into the service hole at the lower right side of lower cover 2 Press the service hole to remove the controller cover 1 Open the air...

Page 57: ...ble to the position for IR receiver kit 2 Lead the connecting cable through the hole for connecting cable 3 Catch 3 hooks of IR receiver kit onto the square holes Pay attention to the direction of IR receiver kit when it is attached NOTE Check whether the IR receiver kit is securely fixed Hook IR Receiver Kit Hook Service Hole Hole for Connecting Cable IR Receiver Kit Attaching Direction for IR Re...

Page 58: ...d supplied wires AWG22 0 3 to 0 5mm2 with soldering Name 3P Connector Cable Model PCC 1A Remarks One set contains five 3P connector cables Specifications Item Specification Model THM R2A Case Material ABS Resin Color Silky White Base Material ABS Resin Color Silky White Sensor Part Name Thermistor Cord Length approx 26 ft 8m 3 9 Remote Sensor THM R2A When a remote temperature sensor is installed w...

Page 59: ...ut 1 Input level signal or pulse signal for voltage from the third party controller or BMS Voltage 12VDC 10mA Voltage 24VDC 10mA Pulse Range 500ms or more Input 2 Third Party Controller or BMS Output 1 Output signal from the wired controller 24VDC From 10mA to 1A Output 2 Refer to the Indoor Unit Manual for Input Output mode setting by the wired controller Refer to Service Manual for connector num...

Page 60: ......

Page 61: ... 20 4 26 1 20 6 26 8 20 9 27 4 21 1 95 22 6 19 2 23 0 19 3 23 5 19 5 24 0 19 7 24 8 20 1 25 6 20 5 26 1 20 6 110 16 2 16 0 15 8 15 6 15 5 15 5 15 2 15 2 15 3 15 3 15 5 15 5 15 5 15 5 114 13 6 13 6 13 5 13 5 13 3 13 3 13 2 13 2 13 2 13 2 13 3 13 3 13 4 13 4 118 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11 2 11 2 11 2 11 2 11 2 11 2 70 31 0 26 0 31 6 26 2 32 3 26 2 32 6 26 4 33 7 27 0 34 6 27 3 35 4 2...

Page 62: ...2 9 22 6 33 24 4 24 4 24 4 24 4 23 9 23 5 37 25 5 25 5 25 4 25 4 24 8 24 3 41 26 5 26 5 26 5 26 5 25 7 25 2 43 27 1 27 0 27 0 27 0 26 2 25 6 47 28 1 28 1 28 1 28 0 27 0 25 6 51 29 2 29 2 29 1 28 8 27 0 25 6 55 30 6 30 2 29 5 28 8 27 0 25 6 59 30 6 30 2 29 5 28 8 27 0 25 6 21 26 7 26 7 26 8 26 8 26 5 26 3 25 28 1 28 1 28 1 28 1 27 7 27 4 29 29 4 29 4 29 4 29 4 28 9 28 5 33 30 7 30 7 30 7 30 7 30 1 ...

Page 63: ...git Unit No Setting RSW2 Units Digit Setting Position Set by inserting slotted screwdriver into the groove Ex Set at No 16 Unit DSW6 RSW2 Set No 1 Pin at ON side Set at 6 3 4 1 0 8 9 2 5 6 7 3 4 1 0 8 9 2 5 6 7 Before shipment DSW6 and RSW2 are set at 0 For the units supporting H LINK II the unit No can be set for Max 64 indoor units No 0 63 3 4 1 0 8 9 2 5 6 7 3 4 1 0 8 9 2 5 6 7 1 2 3 4 5 6 ON O...

Page 64: ... Way Cassette Type Indoor Unit Models H Y C IC4008B21S H Y C IC4012B21S H Y C IC4015B21S H Y C IC4018B21S H Y C IC4024B21S H Y C IC4030B21S H Y C IC4036B21S and H Y C IC4048B21S with Decorative Panel P AP160NA2 ...

Page 65: ...Annex 3 Models H Y C IC4008B21S H Y C IC4012B21S H Y C IC4015B21S H Y C IC4018B21S H Y C IC4024B21S H Y C IC4030B21S H Y C IC4036B21S and H Y C IC4048B21S with Decorative Panel P AP160NAE1 ...

Page 66: ...Annex 4 2 Way Cassette Type Indoor Unit Models H Y C IC2018B21S and H Y C IC2024B21S ...

Page 67: ...Annex 5 1 Way Cassette Type Indoor Unit Models H Y C IC1006B21S H Y C IC1008B21S H Y C IC1012B21S and H Y C IC1015B21S ...

Page 68: ...Annex 6 4 Way Cassette Mini Type Indoor Unit Models H Y C ICM008B21S H Y C ICM012B21S H Y C ICM015B21S and H Y C ICM018B21S ...

Page 69: ...Annex 7 Ceiling Suspended Type Indoor Unit Models H Y C ICS015B21S H Y C ICS024B21S H Y C ICS030B21S and H Y C ICS036B21S ...

Page 70: ...d EconoFresh H Y C IDM030 to 048B21E Wall Mount TIWM006 to 030B22S 2 Way Cassette H Y C IC2018 024B21S 4 Way Cassette Mini H Y C ICM008 to 018B21S 4 Way Cassette H Y C IC4008 to 048B21S 1 Way Cassette H Y C IC1006 to 015B21S Ceiling Suspended H Y C ICS015 to 036B21S 2 Connector Cable Ducted High Static 1st Generation H Y IDH018 to 096B21S PCC CN1925 H Floor Exposed H Y C IFE006 to 015B21S Floor Co...

Page 71: ...nector cable Name Connector Cable Model PCC CN1925 H Remarks One set contains one connector cable Connect the connector cable as shown below Connect the connector cable as shown below During installation refer also to the Installation and Maintenance Manual for connecting indoor unit During installation refer also to the Installation and Maintenance Manual for connecting indoor unit Wired Controll...

Page 72: ... 2018 Johnson Controls Inc TC 18004 rev 2 Code No LIT 12013004 Revised September 2019 ...

Reviews: