ALPA 31 BS 60
25
EN
cod. 3541B530 - 01/2012 (Rev. 00)
4. TECHNICAL DATA AND CHARACTERISTICS
4.1 Dimensions and connections
fig. 28 - Dimensions and connections
1 =
System delivery 3/4”
2 =
Domestic hot water outlet 1/2”
3 =
Gas inlet 1/2”
4 =
Cold water inlet 1/2”
5 =
System return 3/4”
6 =
Recirculation 1/2”
4.2 General view and main components
fig. 29 - General view
5
Sealed chamber
7
Gas inlet
8
Domestic hot water outlet
9
Cold water inlet
10
System delivery
11
System return
14a
Safety valve 3 bar (heating)
14b
Safety valve 9 bar (hot water tank)
16
Fan
19
Combustion chamber
20
Burner assembly
21
Main nozzle
22
Burner
27
Copper exchanger
32
Heating circulating pump
40
DHW expansion tank
44
Gas valve
56
Expansion tank
74
System filling cock
81
Ignition/detection electrode
97
Magnesium anode
102
Air valve
114
Water pressure switch
130
Hot water tank circulating pump
179
Non-return valve
180
Hot water tank
192
Recirculation
221
Bypass cock
233
Hot water tank drain cock
243
Hot water tank temperature sensor
275
Heating system drain cock
278
Double sensor ( Heating)
F11
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F34
Supply voltage under
170V.
Electric mains trouble
Check the electrical system
F35
Mains frequency fault
Electric mains trouble
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Water pressure switch not
connected or damaged
Check the sensor
F39
External probe fault
Probe damaged or wiring
shorted
Check the wiring or replace the sensor
Probe disconnected after
activating the sliding tem-
perature
Reconnect the external probe or disable the
sliding temperature
A41
Sensor positioning
Delivery sensor detached
from pipe
Check the correct positioning and operation
of the heating sensor
F42
Heating sensor fault
Sensor damaged
Replace the sensor
F43
Exchanger protection
activation.
No H
2
O circulation in sys-
tem
Check the circulating pump
Air in system
Vent the system
F50
Modureg fault
Wiring disconnected
Check the wiring
Fault
code
Fault
Possible cause
Cure
850
600
600
821
256
277.5
188
103
55 50 50 50 55 62.5
223
137.5
256
1 5 2 6 4 3
221
97
14
74
180
44
56
243
40
32
233
102
14a
114
16
278
21
27
20
22
19
81
82
5
179
130
275
10 11
7
192 9
8