ALPA 31 BS 60
23
EN
cod. 3541B530 - 01/2012 (Rev. 00)
Adjustment of pressure at burner
Since this unit has flame modulation, there are two fixed pressure values: the minimum
and maximum, which must be those given in the technical data table according to the
type of gas.
•
Connect a suitable pressure gauge to pressure point
"B"
downstream of the gas
valve
•
Disconnect the pressure compensation tube
“H”
and remove the protection cap
“D”
, undoing screw
“A”
.
•
Operate the boiler in
TEST
mode.
•
Set the heating power to 100.
•
Adjust the max. pressure with screw
"G"
, clockwise to increase it and anticlockwise
to decrease it
•
Disconnect one of the two fastons from modureg
"C"
on the gas valve.
•
Adjust the min. pressure with screw
"E"
, clockwise to decrease it and anticlockwise
to increase it.
•
Reconnect the faston detached from the modureg on the gas valve.
•
Check that the maximum pressure has not changed.
•
Reconnect the pressure compensation tube
“H”
.
•
Refit the protection cap
“D”
.
•
To end the
TEST
mode, repeat the activation sequence or wait 15 minutes.
A
After checking or adjusting the pressure, make sure to seal the adjust-
ment screw with paint or a specific seal.
fig. 26 - Gas valve
A
- Protection cap screw
B
- Downstream pressure point
C
- Modureg cable
D
- Protection cap
E
- Min. pressure adjustment
G
- Max. pressure adjustment
H
- Compensation tube
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 3.1). Press the
heating buttons fig. 1 (details 3 and 4 - ) to increase or decrease the power (min. = 00 -
max. = 100). Press the RESET button within 5 seconds and the max. power will remain
that just set. Exit TEST mode (see sec. 3.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 3.1). Press the
DHW buttons (details 1 and 2 - fig. 1) to increase or decrease the power (min. = 00 - max.
= 60). Press the RESET button within 5 seconds and the lighting power will remain that
just set. Exit TEST mode (see sec. 3.1).
Service menu
The card is equipped with two Menus: one for configuration and the other for Service.
The configuration Menu is accessed by pressing the DHW buttons together for 10 sec-
onds. 2 parameters, modifiable only from card, are available.
If replacing the card, always set the parameter P01 to 0=Copper.
To exit the configuration Menu, press the DHW buttons together for 10 seconds.
The card Service Menu is accessed by pressing the Reset button for 10 seconds. Press
the Heating buttons to select "tS", "In", "Hi" or "rE". tS” means Transparent Parameters
Menu, “In” Information Menu, “Hi” History Menu, and “rE” History Menu Reset. After se-
lecting the Menu, press the Reset button to access it.
"tS” - Transparent Parameters Menu
The card is equipped with 24 transparent parameters also modifiable from Remote Con-
trol (Service Menu):
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
The Max. Heating Power and Lighting Power parameters can be modified in Test Mode
(see relevant section).
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" -Information menu
The card can display the following information:
Press the Heating buttons to scroll the list of information. In case of damaged sensor, the card
displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to
exit the Service Menu.
"Hi" - History menu
The card can store the last 10 faults: the History datum item H1: represents the most recent fault
that occurred; the History datum item H10: represents the least recent fault that occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Opentherm re-
mote control.
Press the Heating buttons to scroll the list of faults. Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to
exit the Service Menu.
"rE" - History reset
Press the M button for 3 seconds to delete all the faults and times stored in the History Menu: the
card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button to return to the Service Menu.
Remote control
Card
Description of transparent parameters
Range
Default
NO
P01
Exchanger type selection
0=Copper
1=Cast iron
0=Copper
NO
P02
Boiler shell Warm-up activation temperature
0-80°C
0°C
H
C
D
B
A
D
H
C
E
G
Remote
Control
Card
Description of transparent parameters
Range
Default
01
P01
Gas type selection
0=Natural gas
1=LPG
0=Natural gas
02
P02
Boiler type selection
1=Heating only
2=Storage with probe
3=Storage with ther-
most.
2=Storage with
probe
03
P03
Absolute min. power
0-100%
0%
04
P04
Lighting power
0-60%
50%
05
P05
Not used
Not modifiable
0
06
P06
Heating train
1-20°C/min
5°C/min
07
P07
Heating pump Post-Circulation
0-20 minutes
6 minutes
08
P08
Heating standby time
0-10 minutes
2 minutes
09
P09
Max. heating power
0-100%
100%
10
P10
Pump operation
0=Post-Circulation
1=Continuous
0=Post-Circulation
11
P11
Pump deactivation temperature during Post-
Circulation
0-100°C
20°C
12
P12
Max heating temperature
31-85°C
85°C
13
P13
DHW pump Post-Circulation
0-255 seconds
30 seconds
14
P14
DHW standby time
0-255 seconds
120 seconds
15
P15
DHW max. power
0-100%
100%
16
P16
DHW user max. setpoint
55-65°C
65°C
17
P17
Hot water tank activation hysteresis tempera-
ture
0-20°C
2°C
18
P18
Hot water tank preparation delivery tempera-
ture
70-85°C
80°C
19
P19
Not used
Not modifiable
0
20
P20
Not used
Not modifiable
4 bar/10
21
P21
Not used
Not modifiable
8 bar/10
22
P22
Legionella protection
0-7
0
23
P23
Not used
Not modifiable
0
24
P24
Mains Voltage Frequency
0=50Hz
1=60Hz
0=50Hz
t01
Heating NTC sensor (°C)
between 05 and 125 °C
t02
DHW NTC sensor (°C)
between 05 and 125 °C
t03
Safety NTC sensor (°C)
between 05 and 125 °C
t04
External NTC sensor (°C)
between -30 and 70°C (Negative values flash)
L05
Actual burner power (%)
00%=Min., 100%=Max.
P06
Actual system water pressure (bar/10)
00=Pressure switch open
14= Pressure switch closed
F07
Actual ionisation current (uA)
00=burner off
Summary of Contents for ALPA 31 BS 60
Page 67: ......