GAS SPECIFICATIONS FOR CE APPROVED DRYERS
**
Model
Gas
Type
Nominal
Heating Value
Supply
Pressure
***
Gross
Heat Input
Fuel
Consumption
Orifice Size
Orifice
(Injector)
Quantity
Burner
Pressure
B tu /ft
3
mb
Btu/hr
kW
DMS
mm
mb
SD35
Natural (I
2H
/I
2E
)
1,000
15-30
70,000
20.50
1.981 M
3
/hr
22
3.988
1
9.0
Natural (I
2L
)
830
20-35
70,000
20.50
2.386 M
3
/hr
22
3.988
1
12.0
Natural (I
2ELL
)
830
15-30
70,000
20.50
2.386 M
3
/hr
22
3.988
1
12.0
*
Natural ( I
2E+
)
1,000
20
70,000
20.50
1.981 M
3
/hr
30
3.264
1
—
830
25
70,000
20.50
2.386 M
3
/hr
30
3.264
1
—
*
Butane ( I
3+
)
3,175
28-30
70,000
20.50
1.478 kg/hr
43
2.261
1
—
*
Propane (I
3+
)
2,500
37
70,000
20.50
1.478 kg/hr
43
2.261
1
—
Butane (I
3B/P
)
3,175
28-30/50
70,000
20.50
1.478 kg/hr
41
2.438
1
20.0
Propane ( I
3P
)
2,500
28-30/50
70,000
20.50
1.478 kg/hr
41
2.438
1
25.0
SD50
Natural (I
2H
/I
2E
)
1,000
15-30
125,000
36.64
3.401 M3/hr
5
5.220
1
9.0
Natural (I
2L
)
830
20-35
125,000
36.64
4.098 M3/hr
5
5.220
1
12.0
Natural (I
2ELL
)
830
15-30
125,000
36.64
4.098 M3/hr
5
5.220
1
12.0
*
Natural ( I
2E+
)
1,000
20
125,000
36.64
3.401 M3/hr
17
4.394
1
-
830
25
125,000
36.64
4.098 M3/hr
17
4.394
1
-
*
Butane ( I
3+
)
3,175
28-30
125,000
36.64
2.537 kg/hr
32
2.946
1
-
*
Propane (I
3+
)
2,500
37
125,000
36.64
2.537 kg/hr
32
2.946
1
-
Butane (I
3B/P
)
3,175
28-30/50
125,000
36.64
2.537 kg/hr
30
3.264
1
20.0
Propane ( I
3P
)
2,500
28-30/50
125,000
36.64
2.537 kg/hr
30
3.264
1
25.0
SD80
Natural (I
2H
/I
2E
)
1,000
15-30
135,000
39.53
3.826 M3/hr
2
5.613
1
9.0
Natural (I
2L
)
830
20-35
135,000
39.53
4.610 M3/hr
2
5.613
1
12.0
Natural (I
2ELL
)
830
15-30
135,000
39.53
4.610 M3/hr
2
5.613
1
12.0
*
Natural ( I
2E+
)
1,000
20
135,000
39.53
3.826 M3/hr
14
4.623
1
—
830
25
135,000
39.53
4.610 M3/hr
14
4.623
1
—
*
Butane ( I
3+
)
3,175
28-30
135,000
39.53
2.855 kg/hr
30
3.264
1
—
*
Propane (I
3+
)
2,500
37
135,000
39.53
2.855 kg/hr
30
3.264
1
—
Butane (I
3B/P
)
3,175
28-30/50
135,000
39.53
2.855 kg/hr
29
3.454
1
20.0
Propane ( I
3P
)
2,500
28-30/50
135,000
39.53
2.855 kg/hr
29
3.454
1
25.0
Shaded areas are stated in metric equivalents
*
Gas valve’s internal regulator disabled.
** Consult factory for elevations over 2,000 feet (610 meters) for correct orifice size.
*** Nominal supply pressure.
Heat Input / Gas Consumption / Orifice (Injector) Data (For CE [European] Models Only)
The size of the main gas supply line (header) will vary
depending on the distance this line travels from the gas meter
or, in the case of L.P. gas, the supply tank, other gas-operated
appliances on the same line, etc. Specific information
regarding supply line size should be determined by the gas
supplier.
NOTE:
Undersized gas supply piping can create a low or
inconsistent pressure, which will result in erratic operation
of the burner ignition system.
TYPICAL NATURAL GAS INSTALLATION
TYPICAL L.P. GAS INSTALLATION
Consistent gas pressure is essential at all gas connections.
It is recommended that a 3/4-inch (19.05 mm) pipe gas loop
be installed in the supply line servicing a bank of dryers. An
in-line pressure regulator must be installed in the gas supply
line (header) if the (natural) gas pressure exceeds 13.0 in
WC (32.34 mb) pressure.