18
JLA Limited
113538 - 7
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT
:
NOTES
: A.
B.
C.
When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
SD35
220
1ø
2
—
6.6
15
230
1ø
2
—
6.6
15
240
1ø
2
—
6.6
15
220
3ø
3
—
3
15
230
3ø
3
—
3
15
240
3ø
3
—
3
15
380
3ø
3
—
2.5
15
400
3ø
3
—
2.5
15
416
3ø
3
—
2.5
15
SD50
220
1ø
2
—
5
15
230
1ø
2
—
5
15
240
1ø
2
—
5
15
220
3ø
3
—
4.45
15
230
3ø
3
—
4.45
15
240
3ø
3
—
4.45
15
380
3ø
3
—
2.73
15
400
3ø
3
—
2.73
15
416
3ø
3
—
2.73
15
SD80
220
1ø
2
—
5
15
230
1ø
2
—
5
15
240
1ø
2
—
5
15
220
3ø
3
—
4.45
15
230
3ø
3
—
4.45
15
240
3ø
3
—
4.45
15
380
3ø
3
—
2.73
15
400
3ø
3
—
2.73
15
416
3ø
3
—
2.73
15
Electrical Information _________________
Electrical Requirements
All electrical connections must be made by a properly licensed
and competent electrician. This is to ensure that the electrical
installation is adequate and conforms to local, state, and
national regulations or codes of the country of origin. In the
absence of such codes, all electrical connections, materials,
and workmanship must conform to the applicable requirements
of the National Electrical Code ANSI/NFPA NO. 70-LATEST
EDITION.
IMPORTANT:
Failure to comply with these codes or
ordinances, and/or the requirements stipulated in this
manual can result in personal injury or component failure.
NOTE:
Component failure due to improper installation will
void the warranty.
Each dryer should be connected to an independently protected
branch circuit. The dryer must be connected with copper wire
only. Do not use aluminum wire, which could cause a fire
hazard. The copper conductor wire/cable must be of proper
ampacity and insulation in accordance with electric codes for
making all service connections.
NOTE:
The use of aluminum wire will void the warranty.
An individual ground circuit must be provided to each dryer,
do not daisy chain.
Component failure due to improper voltage application will
void the warranty.
The manufacturer reserves the right to make changes in
specifications at any time without notice or obligation.
IMPORTANT:
A separate protected circuit must be provided
to each dryer.
The dryer must be connected to the electric supply shown
on the rating plate. The supply voltage must match the
electric service specifications of the rating plate exactly.
The wire size must be properly sized to handle the related
current.
!
WARNING
Any damage done to dryer components due to
improper voltage connections will automatically void
the warranty.
Electrical Service Specifications
Gas Models Only
Check your national and local codes for breaker and wire sizes.
10/15/15