Jetter AG
Programming | 7
JX3-BN-EC User Manual
30 / 92
Index
Sub-
index
Description/
Name
Type
Type of
access
Base
Type
Ele-
ment
s
0x1018
Identity
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
:0x01
Vendor ID
UDINT
RO
-
-
:0x02
Product code
UDINT
RO
-
-
:0x03
Revision
UDINT
RO
-
-
:0x04
Serial number
UDINT
RO
-
-
0x10F1
Error Settings
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
:0x01
Local Error Reaction
UDINT
RW
-
-
:0x02
Sync Error Counter
Limit
UINT
RW
-
-
0x1C00
Sync manager type
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
Elements
DT1C00AR
R
RO
USINT
4
0x1C12
SyncManager 2
assignment
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
Elements
DT1C12AR
R
RO
UINT
32
0x1C13
SyncManager 3
assignment
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
Elements
DT1C13AR
R
RO
UINT
32
0x1C32
/
0x1C33
SM output parameter/
SM input parameter
-
-
-
-
:0x00
SubIndex 000
USINT
RO
-
-
:0x01
Synchronization
Type
UINT
RW
-
-
:0x02
Cycle Time
UDINT
RO
-
-
:0x04
Synchronization
Types supported
UINT
RO
-
-
:0x05
Minimum Cycle Time
UDINT
RO
-
-
:0x06
Calc and Copy Time
UDINT
RO
-
-
:0x08
Get Cycle Time
UINT
RW
-
-
:0x09
Delay Time
UDINT
RO
-
-
:0x0A
Sync0 Cycle Time
UDINT
RW
-
-
:0x0B
SM-Event Missed
UINT
RO
-
-
:0x0C Cycle Time Too Small
UINT
RO
-
-
:0x20
Sync Error
BOOL
RO
-
-