Jetter AG
Electrical connection | 6
JX3-BN-EC User Manual
22 / 92
6.3 Commissioning
Engineering of a
JX3 station
A JX3 station consists of a bus node or a controller and the JX3 peripheral mod-
ules connected to it.
INFO
Further information
You will find further information on this topic in chapter
Engineering of a
JX3
station
in the application-oriented manual JX3
System
in the download area of
our
Configuration
Commissioning is based on the following configuration:
2
1
3
4
Fig. 8:
Configuration
Number
Section
Description
1
PC
Programming system
2
Jetter controller
Controller
3
JX3-BN-EC
Bus node
4
JX3 peripheral
modules
Expansion modules
Commissioning
Carry out the following steps to commission the bus node JX3-BN-EC:
ü
You need compatible controller and 2 Ethernet patch cables 1:1 or crossover
with the following transfer rates:
Cat 5e at 10 Mbps to 100 Mbps or Cat 6 at 1.000 Mbps
1.
Make sure that the power supply of the controller and the bus node is
switched off.
2.
Set the IP address of the controller.
3.
On the right side of the bus node snap the expansion modules into it.
4.
Connect controller and PC by means of the Ethernet patch cable.
5.
Connect controller and bus node by means of the Ethernet patch cable.
6.
Energize the controller and the bus node.
ð
Both, the controller and the bus node go through the boot process.
ð
The LED R lits green once the controller and the bus node are ready for
operation.