6 Installation Guide
JetWeb
42
Jetter AG
6.7.2
Description of Connections
Terminal Specifications
• Three-level terminal block COMBICON 5.08.
• Cable cross-sectional area: 0.25 - 2.5 mm
2
• Torque (for input plug screws): 0.5 .. 0.6 Nm
• The maximum stripping length for input lines is 7 mm
• The accepted VDE guidelines have to be observed
• Bladed screw-driver: 0.6 x 3.5 x 100 mm
Connecting Cable Specifications
• Not required
Cable Shielding
• If digital inputs are used as counter.
Note
A digital output may directly (without additional load) be connected to a digital
input.
Pin assignment of 24-pin three-level terminal blocks
View
Pin
Signal
X21
1 - 8 / DC 24V
Sensor power supply DC 24 V
1 / S
Digital input # 1
2 / S
Digital input # 2
3 / S
Digital input # 3
4 / S
Digital input # 4
5 / S
Digital input # 5
6 / S
Digital input # 6
7 / S
Digital input # 7
8 / S
Digital input # 8
1 - 8 / 0V
GND
1
2
3456
7
8
DC
24
V
S
0V
Summary of Contents for JX2-IO16
Page 10: ...Table of Contents JetWeb 10 Jetter AG...
Page 18: ...1 Safety Instructions JetWeb 18 Jetter AG...
Page 22: ...2 Introduction JetWeb 22 Jetter AG...
Page 23: ...JX2 IO16 Jetter AG 23 3 Mounting Dimensions Fig 3 Front View JX2 IO16 Fig 4 Side View JX2 IO16...
Page 24: ...3 Mounting Dimensions JetWeb 24 Jetter AG Fig 5 Top View JX2 IO16...
Page 56: ...6 Installation Guide JetWeb 56 Jetter AG...
Page 68: ...9 Fast inputs Software filter JetWeb 68 Jetter AG...
Page 82: ...10 Pulse stretching JetWeb 82 Jetter AG...
Page 105: ...JX2 IO16 Appendix Jetter AG 105 Appendices...
Page 106: ...Appendices JetWeb 106 Jetter AG...
Page 123: ...JX2 IO16 Appendix Jetter AG 123...