Dual-channel counter
The dual-channel counter is connected as follows:
When connecting the dual-channel counter, make sure that the sensor line are
properly shielded and that the shield is connected with the greatest possible surface
area. The shield is to be connected to a separate grounding bar in close vincinity to
the input terminals. For more information refer to Fig. 12.
Fig. 12: Connecting an incremental encoder
Pin assignment of 24-pin three-level terminal blocks
View
Pin
Signal
X21
5 - 6 / DC 24V
Sensor power supply DC 24 V
5 / S
Dual-channel counter - K1 + / channel
A
6 / S
Dual-channel counter - K2 + / channel
B
5 - 6 / 0V
GND
1
2
3456
7
8
DC
24
V
S
0V
X21
1
2
3
4
5
6
7
8
INPUT
DC
24V
S
0V