Ensure that once the coals have been laid there are even gaps between them. If a coal or coals
appear to fit awkwardly in certain positions then it may be necessary to swap these around with
others or relocate them by rotating to achieve an evenly spaced coal lay. This will ensure an even
flame spread when the fire is lit.
Commissioning
- Turn gas supply OFF, remove inlet pressure test point screw, connect a suitable pressure gauge.
- Turn gas supply ON - check installation for gas soundness.
Burner Operation (Manual / Comfort Control)
- Push the control knob in and turn anti-clockwise until the spark igniter operates.
- Repeat this operation to purge any air from the system until the pilot ignites.
- Keep the knob pushed in for 10-12 secs to energise the flame failure device.
- Release the knob, the pilot should remain alight.
- Depress the knob slightly and turn anti-clockwise as far as it will go to the MAX position. The fire
should light (Unless comfort controller fitted).
- If Comfort Control fitted press LOW on switch panel then ON. The fire should light. Press HIGH
on the switch panel.
- Check the setting pressure - 20.0 mb ± 1.0 mb (cold) MAX.
- Check for gas soundness at all joints with leak detection fluid.
- Turn the appliance OFF
Ɣ
and turn off the gas supply to the fire.
- Remove the pressure gauge and replace the pressure test point screw.
- Check the pressure test point for gas soundness with the gas supply turned ON.
Burner Operation (Remote Control)
- If Remote Control fitted, point the handset to the sensor on the front of the fire. Push and hold the
two ignition buttons together, on the left hand side of the handset. The fire will give out a beep
sound and you can release the buttons. After a few seconds you will hear the clicking spark to the
pilot light. Once the pilot is lit the fire main burner will come on to the high position (this whole
process will take no more than 20 seconds).
- If the burner fails to light repeat this operation to purge any air from the system until the pilot and
main burner ignites.
- Check the setting pressure - 20.0 mb ± 1.0 mb (cold) MAX.
- Check for gas soundness at all joints with leak detection fluid.
- Turn fire off by pointing the handset at the sensor and push the top left button. The fire will go out.
- Remove the pressure gauge and replace the pressure test point screw.
- Check the pressure test point for gas soundness with the gas supply turned ON.