BA-40100-0-V04 | Maintenance Instructions TOPAX DX | 17
Chapter 4: Installation
Menu 0.5: Completing the configuration
The TOPAX DX moves immediately on to the configuration, at the
latest after menu 0.4.11, in the finalising menu (menu 0.5) and
shows the chosen configuration with all the previously chosen
Options in the total overview.
The configuration is saved with the “save” key and the finalis-
ing confirmation key “OK” and the TOPAX DX moves to the next
menu 0.6.1.
The configuration starts from the beginning again with the key
“back”. The TOPAX DX goes back to menu 0.4.1.
news configuration
free chlorine
potentiostat
3 point step with poti
ph value
Impulsefrequency (relais)
combined chlorine
flocculation
impulsefrequency (opto)
DIN-contact
OFF
save
impulselength (relais)
back
conductivity sensor
impulselength (relais)
0.5
REDOX
temperature
on
on
eco control
off
flow input
off
Menu 0.5: Total overview over all selected options.
Menu 0.6: Terminal connections
According to the chosen Options the TOPAX DX determines the
relevant terminal connections and shows this in menus 0.6.1 to
0.6.4 (each by number of connections).
free chlorine
input clamps analog
next
check clamps and setup
pH value
REDOX
temperature
new configuration
total chlorine sensor
71 - 72 - 73
53 - 54
55 - 56
57 - 58
51B - 52B
0.6.1
connect only with
main voltage off
Menu 0.6.1: Example of a new configuration and the relevant terminal connec-
tion plan.
NOTE!
Make a note of the given connections on the pre-
print in chapter 24.
In order to move between the individual menus 0.6.1 to 0.6.4,
press either the “next” or the “back” key, or the arrow keys
▲
and
▼
.
To finalise the total configuration confirm the connection plan
with the “OK” key. The TOPAX DX then moves to the standard
display (see fig. 4.19).
You can find further information on the structure of the Menus for
the TOPAX DX in chapter 16.
mg/l
mV
ºC
comb. cl.
temp.
REDOX
free chlorine
pH value
7.04
0.39
719
mg/l
0.09
26.3
eff. cl.
0.30 mg/l
Topax DX
14:28 06.02.2007
Fig. 4.19: Standard display with the most important measuring values.
NOTE!
After confirming the pre-settings, TOPAX DX starts
up. At start-up the controller outputs of your TOPAX
DX will be function-less for approx 60 seconds. This
time is needed for the stabilization of the electro-
chemical sensors. During this time the status display
shows the message „starting in..... s“ (countdown
seconds are progressively shown). At the end of this
time TOPAX DX is fully operative. All data shown on
the various menus are displayed in clear text.
NOTE!
It is possible to protect your setting against unaut-
horized change by use of a personal password (see
Chapter 16, Menu 5.9).
4.9 Next steps of configuration
After a successful configuration the next steps should be:
• Mount the device
• Attach the sensors and actuating element (to the controlling
pumps and switch, etc.)
• Calibrate the sensors to the measuring output (see chapter
5 and 6)
• Set up the target value of the measuring input (see chapter
16, menu 1.1)
• Set up the control (see chapter 16, menu .1)
• Configuration of the regulating output (see chapter 7)
NOTE!
You can repeat the software-configuration during the
normal operation (see chapter 6, menu 5, „configu-
ration“). Here the changes to the terminal plan are
written in red figures.