34  |  BA-40400-02-V14

Two-Channel Controller TOPAX DE

For night-time operation:
•  only useful in a closed circuit.
•  it can be manually switched on and off.
•  the target value for the controller has to be defined.
•  the percentage value can be set for reduction of recirculation 

power.

•  Configuring the timer is not possible.

12.1.13 Menu 5: Service

configuration

flocculation

inputs

autosetup

clock

DIN-contact

network

code

HW - Status

restart

timer
service code

logfiles

outputs

ESC

recorder

alarm action

startup

digital inputs

language

display

5

mg/l

pH

°C

26.3

7.04

0.39

Fig.33: Main menu >> menu 2 >> service

The Menu 5 “Service” covers 20 functions for the basic setting of the 
TOPAX (not all functions are available):

Menu

Key

Function

0.4.4

Configuration

Repeat basic configuration
Saving and loading of a configuration

5.01

Hardware status

Hardware/software equipment

5.1

Inputs

Adjusting the input measuring ranges

5.2

Outputs

Outputs settings

53

Auto setup

not available

5.4

Reset

Reset and factory settings

5.5

Network

Configuration of RS 485 network address 
(optionally available)

5.6

Logbook

Write/read the logbook

5.7

Time

Setting of date and time

5.8

Timer

not available

5.9

Password

Definition of an access code for the individual 
menus

5.10

Service password Setting an access code for menu 5 "service"

5.11

DIN contact

not available

5.12

Flocculation

not available

5.13

Alarm settings

Configuration of alarm settings

5.14

Start

Setting the start delay

5.15

Recorder

0...20 mA/4...20 mA or test signal selection

5.16

Digital inputs

Digital input settings

5.17

Display

Display settings

5.18

Language

Change language and units

The various menus are described in the following pages.
To select the menus press the arrow keys 

 and 

. Confirm the 

selection with “OK”.

12.1.14 Menu 0.4.0: Configuration 

The configuration of TOPAX can be changed, saved and loaded. Existing 
configuration files are saved on the memory card or loaded from it.
Main menu >> menu 2 >> service >> configuration ...
... >> edit  

Menu 0.4

... >> Load 

Menu 0.4.20, select an existing configuration  

  with 

the 

 and 

 keys and confirm with "OK".

... >> save  

Menu 0.4.21, save the current configuration to  

 

 

the memory card. The file name can be chosen  

  freely.
In this way, the configuration of the TOPAX can for instance be done for 
several control circuits once and then be transferred to other, identical 
TOPAX controllers via the memory card. All settings are transferred.
Furthermore, the configuration files can be saved on a PC and trans-
ferred to an identical TOPAX if required.

12.1.15 Menu 0.4.1: Configuration

next

ESC

CS120 cell (direct)

potentiostat

membrane covered cell
REDOX-Sensor

0.4.1

input disinfection

total chlorine sensor

Fig.34: Main menu >> menu 2 >> service >> configuration >> edit

IMPORTANT!

The disinfection input will be preset before delivery accord-
ing to the order and can no longer be changed.

The configuration of inputs and outputs can be modified if 
necessary. Before it is saved, the newly set configuration 
is indicated in red and must be saved. Use the "ESC" but-
ton to exit the menu without saving and return to the old 
configuration.

When the new configuration is saved, check the terminals as well. The 
new wiring diagram is displayed. The changed terminals are shown in 
red writing. The terminal plan must be confirmed.
Inadmissible configurations are blocked. A text error message is shown.
For control purposes the terminal layout and assignments can be seen 
in menu 5.01 “Hardware status”.
All TOPAX versions are supplied with a measuring protocol and a termi-
nal connection diagram referred to the actual configuration.

Summary of Contents for TOPAX DE

Page 1: ...TOPAX DE Two Channel Controller EN 01 Operating instructions Read this operating manual before using the equipment To be retained for future reference...

Page 2: ...tion amperometric measurement cells 20 5 2 pH value measurement input 21 5 3 Measurement output Redox potential 23 5 4 Temperature measurement input 23 6 Explanation of digital signal inputs 24 6 1 St...

Page 3: ...behalf of the operating company The operating company must also ensure that the operating manual has been under stood 1 4 Electrical device safety instructions Basic safety precautions should always b...

Page 4: ...nd obtaining spare parts TOPAX may be converted or changed only by qualified technical person nel If the configuration of the TOPAX is wrongly made by assembly or ser vice personnel errors and dangers...

Page 5: ...als Total chlorine measuring input Encapsulated electrode Measuring range adjustable from 0 1 00 mg l 0 2 00 mg l or 0 10 mg l Disturbance variable input option ally available 0 20 mA or 4 20 mA Distu...

Page 6: ...mm 8 7 mm Relay output alarm M16 X 1 5 NYM O 3x 1 5 mm 9 1 mm connection to PC computer cable Cat 5 M12 X 1 5 Type 2X2XAWG24 1 5 7 mm Connection of current outputs remote communication cable M12 X 1 5...

Page 7: ...ts are removed at the same time the front housing will no longer be attached to the bottom section ATTENTION The equipment must only be opened when it is dis connected from the power supply 4 2 Dimens...

Page 8: ...he software configuration automatically assigns these outputs to the respective terminals in a sequential order depending on the configura tion of the TOPAX 1 Disinfection controller 2 Controller pH v...

Page 9: ...ate the RS 485 resistances on the last TOPAX in the network 4 4 6 TopView software For remote viewing on a PC the manufacturer offers the full version of the TopView display program and a freeware ver...

Page 10: ...must be clean and dry The permissible bending radius of the cable must be respected The quality of the holding wires must correspond to the defaults from the data sheet of the sensor IMPORTANT If pos...

Page 11: ...surement output 0 4 20 mA Redox 6 7 Measurement output 0 4 20 mA Temperature or programmed as controller output 8 9 Measurement output 0 4 20 mA combined chlorine or programmed as controller output 10...

Page 12: ...r polarity of clips 59 and 61 at wish 60 Driver 61 4 7 3 Input module 3x Terminal Function Cable colour 71 Reference electrode with integrated cable Disinfection potentiostatic measuring cell Referenc...

Page 13: ...71 72 73 7 pH Single Rod Measuring Cell PE110 pH 52 53 8 Redox Single Rod Measuring Cell ME110 ORP 54 55 9 Reference Electrode for Potentiostat SS Electrode for Potentiostat 1 4571 Gold Electrode for...

Page 14: ...rrent output Current output 20mA analogue accessories Menu configuration 0 6 3 DANGER Open the housing of the TOPAX controller with disconnected power supply only Secure the power supply to prevent it...

Page 15: ...54 55 61 51B 52B 71 72 73 74 75 76 77 78 39 40 41 43 44 45 46 42 35 95 96 A B A B pH value dosing pump PC interface Temperature pH value Redox 90 264 V AC Input module 5 fold CPRT ATE 5 fold Power sup...

Page 16: ...12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 36 37 38 PE N L 33 34 92 93 94 87 88 89 90 91 86 81 82 83 84 85 56 57 58 59 60 51A 52A 53 54 55 61 51B 52B 71 72 73 74 75 76 77 78 39 40...

Page 17: ...1 First set up and programming guidelines After correct installation switch on the power supply The TOPAX is programmed by the manufacturer based on customers specs before shipment and is supplied alo...

Page 18: ...highlighted in grey To go back to the previous menu press the key back or 4 11 10 Menu 0 5 Completing the configuration The TOPAX moves immediately on to the configuration at the latest after menu 0 4...

Page 19: ...hemical and physical correlations which are necessary to understand the behaviour of the measurement inputs The measurement inputs are processed for Disinfection pH value Redox potential Temperature A...

Page 20: ...d using a two point calibration see section 12 1 5 Menu 1 2 Calibration on page 30 The physical measurement A measured on the measuring cell is shown on the display during calibration Reference value...

Page 21: ...4 20 mA Whenever your TOPAX fea tures a lower value than 3 5 mA an alert message is displayed total chlorine sensor failure the alarm relay is switched 5 2 pH value measurement input 5 2 1 Technical d...

Page 22: ...ble and the plug connectors If the zero point and transconductance values of the single rod measuring cell exceed the tolerances the system notifies the operator with a warning mes sage The measuring...

Page 23: ...ixed buffer solution value The deviation should not exceed 10 approximately The plausibility of the transconductance measurement is monitored throughout the process After a reaction time approx 1 minu...

Page 24: ...tal inputs are activated the level switches must be connected to the terminals respectively If no level switch is at tached the inputs are to be deactivated 7 Explanation of measuring values outputs 7...

Page 25: ...ed current 0 4 20 mA or control outputs with pulse frequency The latter can be controlled as electronic optocoupler or relay outputs 8 Controller explanation 8 1 Definitions Term Definition actual val...

Page 26: ...nd Ph close to the setpoints within tight limits e g for bathing the control ler must be adjusted to the controlled system This is achieved via the control parameters Xp for the proportional area Tn f...

Page 27: ...f 20 of the control range 8 8 Manual mode Controllers can be manually adjusted If a controller is manually operated this will be indicated by a large M behind the Y in the status displays and the Y di...

Page 28: ...nually adjusted to the actuator independently of the settings in the service menu recorder It is possible to configure the 0 20 mA controller output and a 4 20 mA recorder output It must be noticed th...

Page 29: ...ecorder night mode service 2 mg l pH C 26 3 7 04 0 39 Fig 20 Menu 2 Extension of the main menu 12 1 3 Overview of the sub menus You can access all other sub menus through the main menu menu 1 and the...

Page 30: ...electrode Menu 1 2 1 3 Encapsulated electrode Menu 1 2 1 pH value pH single rod measuring cell without specifications about slope rate Menu 1 2 2 pH single rod measuring cell with specifications abou...

Page 31: ...1 4 2 Switching status of all outputs 1 4 3 Physical values and calibrated resistivity values of all inputs 1 4 4 used software version serial number hardware identification data input identification...

Page 32: ...Xp value 2 1 2 3 2 Parameter Tn ON or OFF time 2 1 2 3 3 Parameter Tv ON or OFF time 2 1 2 4 Basic load ON or OFF time 2 1 2 5 Manual mode value ON OFF Select one of the two control units The device g...

Page 33: ...digit of the limit value is highlighted in grey and can be ad justed Use the arrow keys to set up the value switch over between the individual positions alter numerical values Confirm the entry by pr...

Page 34: ...s To select the menus press the arrow keys and Confirm the selection with OK 12 1 14 Menu 0 4 0 Configuration The configuration of TOPAX can be changed saved and loaded Existing configuration files ar...

Page 35: ...rd Main menu menu 2 service password and service password In these menus you can block the various levels by using a password a 4 digit numerical code All information menus remain available The passwo...

Page 36: ...a system name on the display Switching on off additional information on the standard display Setting the brightness of the display 12 1 29 Menu 5 18 Language Main menu menu 2 service language User lan...

Page 37: ...OFF 14 Memory card The memory card transfers and stores language data and logfiles The data which is saved on the card can be transferred to a PC by means of a reading device To remove the memory card...

Page 38: ...xceeded Activated configurable Min alarm Measurement below set level Activated configurable Y alarm Safety cutout see item 9 2 Activated configurable 15 3 Remedy Display Reason Remedy System start Sys...

Page 39: ...t Disinfection Types of output Terminal connection clips Servomotor with potentiometer Motor Potentiometer with position feedback Servo motor without potentiometer Pulse frequency Optocoupler Pulse fr...

Page 40: ...27 28 OK closed OK opened Not active 17 Device revision This operating manual applies to the following devices Device and model Revision status Software Version TOPAX 1 2013 1 25 onwards Language file...

Page 41: ...t person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions of the device Point of use system designation Access...

Page 42: ...ualquier modificaci n en la presente mercanc a sin nuestra previa autorizaci n esta declaraci n pierde su validez NL EU overeenstemmingsverklaring Ondergetekende Lutz Jesco GmbH Am Bostelberge 19 3090...

Page 43: ...ata 5 H Hardware status 35 Housing 7 I Inputs module 8 Installation 7 K Key layout 17 L Language 36 Level dosing pump 24 Level inputs 24 Logbook 28 M Manual mode 27 Measurement input Disinfection 20 m...

Page 44: ...com Internet www lutz jescoasia com sterreich Lutz Jesco GmbH Aredstra e 7 2 2544 Leobersdorf Austria Tel 43 2256 62180 Fax 43 2256 6218062 E Mail info lutz jesco at Internet www lutz jesco at Middle...

Reviews: