32 | BA-40400-02-V14
Two-Channel Controller TOPAX DE
Enter the name of the pre-adjustment using the arrow keys
▲
and
▼
.
This means:
Keys
Function
▲
and
▼
:
Change individual letters and numbers
◀
and
▶
:
shift cursor
ab <=> 01 change small letters to numbers/symbols
ab <=> AB change small into capital letters
Press the “save” key to save up to this point the adjusted regulating
characteristics. Confirm the procedure with the “OK” key.
The following adjustments are saved and can be re-activated at any
time:
• regulating characteristics of configured controller
• set values of configured controller
12.1.8 Menu 2.1: adjust controller
setup
controller
2.1
mg/l
pH
°C
26.3
7.04
0.39
pH value
disinfection
ESC
Fig.28: Main menu >> menu 2 >> controller
The TOPAX is able to command up to four control units. The basic ad-
justments of every single control unit are configured in this menu:
Menu
Controller setting
Required specifications
2.1.1
Disinfection
2.1.1.1
Control direction
boosting/dropping/2 sites
2.1.1.2
Disturbance variable
Disturbance variable, ON/OFF
2.1.1.3
overview of settings
2.1.1.3.1
Parameter Xp
% value
2.1.1.3.2
Parameter Tn
ON or OFF + time
2.1.1.3.3
Parameter Tv
ON or OFF + time
2.1.1.4
Basic load
ON or OFF + time
2.1.1.5
Manual mode
%-value, ON/OFF, shock
chlorination
2.1.2
pH value
2.1.2.1
Control direction
boosting/dropping/2 sites
2.1.2.2
Disturbance variable
Disturbance variable, ON/OFF
2.1.2.3
overview of settings
2.1.2.3.1
Parameter Xp
% value
2.1.2.3.2
Parameter Tn
ON or OFF + time
2.1.2.3.3
Parameter Tv
ON or OFF + time
2.1.2.4
Basic load
ON or OFF + time
2.1.2.5
Manual mode
%-value, ON/OFF
Select one of the two control units. The device goes to the
relevant menu 2.1.1… 2.1.2.
Apply the adjustments relevant to your requirements in the fol-
lowing sub-menus to the control unit.
Adjust the parameters accordingly with the arrow keys
▲
and
▼
and confirm your entries with the "OK" key.
12.1.9 Configuring the shock chlorination (only in case of disin-
fection with chlorine)
For shock chlorination, the "Disinfection" controller is switched to manu-
al operation for an adjustable time and an adjustable dosing rate. When
the time has elapsed, the controller automatically switches to automatic
operation.
NOTICE!
The user must empirically define the time and the
dosing rate for shock chlorination before this func-
tion is performed.
manual mode
100 %
controller 1
disinfection
2.1.1.5
(OK) to store
6 min
Timer 200 s
mg/l
pH
°C
26.3
7.04
0.39
%
time
ESC
off
shockchl.
on
Fig.29: Main menu >> menu 2 >> controller >> Disinfection >> manual
>> shockchl.
The "shock chlorination" key is used at the same time for configuring
and starting shock chlorination. Set the time with the "Time" key. Set the
maximum output capacity with the "%" key.
Press the "OK" key to save the settings. The shock chlorination is indi-
cated on the status display. The timer counts down and indicates the
remaining time in minutes. When the time has elapsed, the system
switches to automatic operation.
12.1.10 Menu 2.2: Alarms
setup
alarms
2.2
mg/l
pH
°C
26.3
7.04
0.39
temperature
pH value
disinfection
ESC
Fig.30: Main menu >> menu 2 >> alarms