BA-40400-02-V14 | 37
Operating instructions
13 Default settings
The default configuration by the manufacturer includes the following
settings. The inputs are activated according to the part number.
• Y-Alarm (safety stop)
works for all controllers and lasts 60 minutes
• Start-up lag time: Time 60 seconds
• all measuring alarm values are deactivated
• all special functions are deactivated
Digital signals
• measuring water alarm: •
ON when the contact is opened
• night-time reduced operation • ON when the contact is closed
• Level inputs:
Input not active
Input Disinfection
In the as-delivered state
Disturbance factor input
Output Disinfection
Servomotor with potentiometer
pH output
Pulse frequency (optocoupler) 100 pulses/min
Disinfection controller
W: 0.50 mg/l
Xp: 35 %
Tn: 15 minutes
Tv: OFF
Controller pH value
W: pH 7,10
Xp2: 10 %
Tn2: 15 minutes
Tv2: OFF
14 Memory card
The memory card transfers and stores language data and logfiles.
The data which is saved on the card can be transferred to a PC by
means of a reading device. To remove the memory card, the TOPAX
must be switched off in a specific way: press the "Switch Off" key in
the "Service-reset" menu. All controllers are set to an output capacity of
"0%" and all unsaved data is saved to the memory card. The TOPAX can
continue to operate without the card.
Fig.35: Slot for the memory card on the display board. The card is inserted on
the display circuit board in the front housing.
ATTENTION!
The memory card must only be inserted or removed
when the device is de-energised. Switch off the
TO-
PAX
in the "Service-reset" menu.
On its website, the manufacturer provides the free software "TopRead-
er" to read the memory card with the recorder and configuration data.
ATTENTION!
Make sure that no additional data is saved on the
memory card
and that the saved data is not modified (data loss). The
memory
card
must only be formatted in "FAT" format.