2.4.9
Outdoor
Combustion Air Kit
In snowy climates, the air intake hood should be located 30cm (12’’) above the maximum snow level
for that climate or a minimum 1.2m (48’’) above ground level and be sheltered from high winds.
Place the exit of the combustion air intake in the room where the fireplace is installed or in an
adjacent connecting room as per ANSI Z 223.1/NFPA 54.
Caution: the Outside Combustion Air intake must not come from an attic, garage, carport, basement,
the chimney’s enclosure or be less than 3m (10’) from a gas meter, a fuel/propane tank or any other
device that may emit fumes or gases, such as the exhaust of a motor vehicle.