33
Note: the auto pH is automatically deactivated when the pH set point is changed to values
outside the auto-pH curve and when the valve is set to “man“.
Hysteresis
Open with the following steps:
Settings key > select Hysteresis > press OK > enter desired value using “plus” and “minus” >
press OK.
Hysteresis shows the switching points. In order to avoid the unnecessarily frequent switching
on and off of the solenoid valve, an upper and lower limit is set by which the measured
pH value may deviate from the pH set point before the solenoid valve switches on. This
saves wear and tear on the solenoid valve. You can find an example for the control mode in
chapter 5.1. Values from 0.1 up to 0.5 pH units can be selected. Factory setting: 0.1 pH
Valve
Open with the following steps:
Settings key > select valve > press OK > select auto, man open or man shut > press OK.
The operation mode of the integral solenoid valve can be selected in this menu item. The
options are automatic operation (auto) and manual open (man open) as well as manual shut
(man closed). In order for the device to control, the “auto“ setting (factory setting) must be
selected.
For the settings “man open “ and “man closed“, the valve stays open or shut until the setting
is changed.
A green symbol for “open“ or a red symbol for “shut“ and “A“ for automatic or “m“ for manual
appear on the value overview (chapter 4).
DE
UK
FR
NL
IT
ES
PT
SE
CZ
PL
RU
RO
TR
Summary of Contents for PROFLORA pH Control Touch
Page 2: ...1 a...
Page 3: ...2...
Page 4: ......
Page 8: ...4 Kalibrierung...
Page 29: ...25 DE UK FR NL IT ES PT SE CZ PL RU RO TR Calibration...
Page 50: ...46 talonnage...
Page 71: ...67 Kalibratie DE UK FR NL IT ES PT SE CZ PL RU RO TR...
Page 92: ...88 Calibratura...
Page 113: ...109 DE UK FR NL IT ES PT SE CZ PL RU RO TR Calibraci n...
Page 134: ...130 Calibra o...
Page 155: ...151 DE UK FR NL IT ES PT SE CZ PL RU RO TR Kalibrering...
Page 195: ...191 DE UK FR NL IT ES PT SE CZ PL RU RO TR Kalibracja...
Page 216: ...212...
Page 217: ...213 7 00 4 00 calibration o k 4 2 3 7 1 7 13 30 CO DE UK FR NL IT ES PT SE CZ PL RU RO TR...
Page 218: ...214 6 5 4 3 2 1 7 8 9 10 11 12 13 1 2 3 4 5 Auto pH KH 6 7 8 9 10 11 CO 12 13 Auto pH...
Page 226: ...222 OK 0 10 2 00 0 05 1 00 CO 0 50 CO 20 C t 30 C 4...
Page 228: ...224 OK locked unlocked OK locked OK OK 7422 4 software version Software Version OK...
Page 230: ...226 4 5 2 sensor defect DELTAV OFFSET DELTAV 35 7 00 OFFSET pH 7 00 4 00 7 00...
Page 232: ...228 24 JBL 2 3 JBL JBL pH Sensor 24 JBL JBL PROFLORA pH...
Page 238: ...234 Calibrare...
Page 259: ...255 DE UK FR NL IT ES PT SE CZ PL RU RO TR Calibration Kalibrasyon...
Page 277: ...273...