86
UMG 96RM
100
SHORT
RD/WR
-
Address of the measured value,
Digital output 1
0..32000
0
101
SHORT
RD/WR
-
Address of the measured value,
Digital output 2
0..32000
0
102
FLOAT
RD/WR
Wh
Pulse value,
Digital output 1
-1000000..+1000000 0
104
FLOAT
RD/WR
Wh
Pulse value,
Digital output 2
-1000000..+1000000 0
106
SHORT
RD/WR
10ms
Minimum pulse length (1=10 ms)
Digital output 1/2
1..1000
5 (=50 ms)
107
SHORT
RD/WR
-
Result from comparator group 1;
0,1
0
Link A, B, C
(1=and,
0=or)
108
FLOAT
RD/WR
-
Comparator 1A, Limit value
-1000000..+1000000 0
110
SHORT
RD/WR
-
Comparator 1A,
Address of the measured value
0..32000
0
111
SHORT
RD/WR
s
Comparator 1A,
Minimum turn-on time
0..32000
0
112
SHORT
RD/WR
s
Comparator 1A, Lead time
0..32000
0
113
SHORT
RD/WR
-
Comparator 1A, Operator
0,1
0
“>=”=0, “<”=1
114
FLOAT
RD/WR
-
Comparator 1B, Limit value
-1000000..+1000000 0
116
SHORT
RD/WR
-
Comparator 1B,
Address of the measured value
0..32000
0
117
SHORT
RD/WR
s
Comparator 1B,
Minimum turn-on time
0..32000
0
118
SHORT
RD/WR
s
Comparator 1B, Lead time
0..32000
0
119
SHORT
RD/WR
-
Comparator 1B, Operator
0,1
0
“>=”=0
“<”=1
Address
Format
RD/WR
Unit
Note
Adjustment Range Default
C
Only the first three positions (###) of a value are shown on the display. Values larger than
1,000 are marked with „k”. Example: 003k = 3000