90
UMG 96RM
Table 2 - Modbus address list
(frequently used measured values)
19000
808
float
RD
V
Voltage L1-N
19002
810
float
RD
V
Voltage L2-N
19004
812
float
RD
V
Voltage L3-N
19006
814
float
RD
V
Voltage L1-L2
19008
816
float
RD
V
Voltage L2-L3
19010
818
float
RD
V
Voltage L3-L1
19012
860
float
RD
A
Current, L1
19014
862
float
RD
A
Current, L2
19016
864
float
RD
A
Current, L3
19018
866
float
RD
A
Vector sum; IN=I1+I2+I3
19020
868
float
RD
W
Real power L1
19022
870
float
RD
W
Real power L2
19024
872
float
RD
W
Real power L3
19026
874
float
RD
W
Sum; Psum3=P1+P2+P3
19028
884
float
RD
VA
Apparent power S L1
19030
886
float
RD
VA
Apparent power S L2
19032
888
float
RD
VA
Apparent power S L3
19034
890
float
RD
VA
Sum; Ssum3=S1+S2+S3
Modbus Address
Address
Above display Format
RD/WR
Unit
Note
C
A complete overview of the parameters and
measured values is given in the "Modbus
Address List" document on the CD or on
the Internet.
C
The addresses in the range from 0-999
listed in this document can be adjusted
directly on the device. The address range
over 1,000 can only be edited via Modbus!