25
UMG 96RM-M
• 1p 2i (addr. 510 = 6)
I1
I2
I3
L1
L2
L1
L2
L3
N
I1
I2
I3
• 3p 3w (addr. 510 = 4)
• 1p 2w (addr. 510 = 7)
L1
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3
• 2p 4w (addr. 510 = 5)
Fig. Measured values derived from the I3 current
measurement input are assumed to be zero and
not calculated.
Fig. Measured values derived from the I2 and I3
current measurement inputs are assumed to be
zero and not calculated.
Fig. System with uniform phase loading. The
measured values for the I2 current measurement
input are calculated.
Fig. System with uniform phase loading. The
measured values for the I2 and I3 current
measurement inputs are calculated.